期刊文献+

一起光纤复合架空地线雷击故障的分析探讨

Analysis and Discussion on a Lightning Fault of Optical Fiber Composite Overhead Ground Wire
下载PDF
导出
摘要 介绍了江苏宿迁地区发生的一起光纤复合架空地线(OPGW)断缆导致通信骨干业务中断的故障,根据断缆区域和光纤中断警告时间和GPS雷电定位系统检索,可判断该OPGW断缆为雷击所致。通过观察分析,雷电弧高温发生在绞线层和线间,为了提高OPGW的耐雷水平,建议500 kV和重要骨干电路尽量采用层绞结构OPGW光缆。 A cable-broken fault on optical fiber composite overhead ground wire (OPGW) in Suqian area of Jiangsu province is introduced, which led to the interruption of key communication. Based on the fault area, alarm time and the search of GPS lightning location system, the cause is considered as lightning. According to the observation and analysis, high temperature resulting from lightning electric located between stranded wire and stranded wire layer. In order to improve lightning resistance ability of OPGW, OPGW with stranded wire layer structure is suggested to adopt for 500 kV and key circuits.
机构地区 宿迁供电公司
出处 《江苏电机工程》 2009年第5期16-17,共2页 Jiangsu Electrical Engineering
关键词 OPGW光缆 雷击 耐雷击水平 OPGW cable lighting strike lightning resistance abilit
  • 相关文献

参考文献5

二级参考文献23

  • 1陈永诗.光纤类型、标准和最新发展(上)[J].电力系统通信,2004,25(9):1-4. 被引量:2
  • 2.GB/T 8999—1999.光复合架空地线[S].,1999..
  • 3.IEEE Std 1138-2001.用于电力线路的光纤复合架空地线的IEEE标准[S].,..
  • 4付宾兰.关于OPGW遭雷击的有关问题[A]..电力特种光缆应用技术会议论文集[C].,2001.4-15.
  • 5日本日立电线株式会社.雷击断股分析报告[R].,2000.5.
  • 6.中天日立OPGW在加拿大Kinectrics实验室雷击试验报告[R].,2001..
  • 7IEC 60 94-4- 1 - 1999.Optical Fibre Cables Part4 - I :Aerial Optical Cables for High-Voltage Power Line[S] .1999.
  • 8IEC 60794 - 4 - 1 - 1999. Optical Fiber Cable Part 4 - 1:Aerial Optical Cable for High-Voltage Power Line [ S ]. 1999/2003.
  • 9William A Chisholm, Jody P Levine, Lightning Arc Damage to Optical Fiber Ground Wires ( OPGW ): Parameters and Test Methods[ S]. IEEE 2001.
  • 10F Meier,N Nibble. Et Effect Of Lighting Flashes On Overhead Power Ground Wires With Optical Fibers [ Z ]. CIRED 1995.