期刊文献+

不对称短路时电抗型故障限流器对暂态稳定性的影响 被引量:9

Influences of Reactance-Type Fault Current Limiter on Power System Transient Stability With Asymmetrical Short-Circuit Faults
下载PDF
导出
摘要 针对单机对无穷大系统,提出了在输电线路不同位置发生不对称短路故障时,故障限流器(FCL)投入电抗后对暂态稳定性影响的分析方法。基于功角特性曲线分别详细分析了在单相接地短路、两相接地短路和两相短路故障下电抗型FCL对暂态稳定的影响情况。通过对接入电抗型FCL的电力系统进行不同类型故障下的暂态稳定时域仿真研究,验证了分析结论。 Transient stability of a single machine to infinite-busbar power system with reactance-type fault current limiters (FCL) is analyzed under asymmetrical short-circuit fault conditions. The FCL is considered to introduce a reactance into the three-phase circuits when faults occur. Based on the power-angle curves for different short-circuit conditions - the single-line to ground, double-line to ground and double-line short-circuit faults, the influences of the FCLs to transient stability is analyzed in details. The time-domain simulation of transient stability is carried out to verify the analytical results.
出处 《电工技术学报》 EI CSCD 北大核心 2009年第9期86-92,共7页 Transactions of China Electrotechnical Society
关键词 电抗型FCL 暂态稳定 功角 电力系统 Reactance-type FCL, transient stability, power angle, power systems