《商业或工业用的蒸发型冷气机》标准制定的若干问题探讨 被引量:4

Discussion on some problems in establishing the standard of Commercial or industrial evaporative air-conditioners
下载PDF
导出
摘要 通过对我国干燥地区、沿海高相对湿度地区代表性城市典型气象年气象数据的分析,选定蒸发型冷气机干燥地区名义工况的干湿球温度为38℃/23℃,高相对湿度地区名义工况的干湿球温度为38℃/28℃。通过分析蒸发型冷气机的供冷量,采用等效处理方法得到了供冷量的计算方法,为标准的供冷量、能效比的计算和试验方法的确定提供了参考。 With an analysis of typical meteorological year data in some representative cities in China's dry areas and highly humid coastal areas,selects 38 ℃/23 ℃ as the dry bulb temperature and wet bulb temperature of the nominal condition in dry areas and 38 ℃/28 ℃ in coastal areas with high relative humidity.By an analysis obtains the calculation method of the cooling capacity of evaporative air-conditioners,and provides a reference for the determination of the cooling capacity,energy efficiency ratio and testing method.
出处 《暖通空调》 北大核心 2009年第9期20-23,共4页 Heating Ventilating & Air Conditioning
基金 西安工程大学研究生创新基金资助项目(编号:chx090711)
关键词 蒸发型冷气机 标准 名义工况 制冷量 能效比 evaporative air conditioner standard nominal condition cooling capacity energy efficiency ratio
  • 相关文献

参考文献6

二级参考文献113

共引文献183

同被引文献33

  • 1檀志恒,强天伟,沈恒根.蒸发冷却空调在工业厂房的应用研究[J].制冷与空调(四川),2006,20(2):63-66. 被引量:9
  • 2黄翔.国内外蒸发冷却空调技术研究进展(1)[J].暖通空调,2007,37(2):24-30. 被引量:161
  • 3卫生部(GBZ1-2002).工业企业设计卫生标准[S].2002.
  • 4黄翔.中国蒸发冷却空调设备行业分析报告[R].2009.
  • 5蒸发式冷气机国家标准起草工作组.蒸发式冷气机[S] (征求意见稿).2008.
  • 6合肥通用机械研究所、广东省吉荣空调设备公司.GB/ T 17758 -1999 单元式空气调节机[S].1999.
  • 7合肥通用机械研究所.GB 9068-1988 采暖通风与空气调节设备噪声声功率级的测定工程法[S].1998.
  • 8沈阳鼓风机研究所.JB/T 8690-1998 工业通风机噪声限值[S].1998.
  • 9蒸发式冷气机国家标准起草工作组.蒸发式冷气机[S]. (征求意见稿).2008.
  • 10安洪萍 催远勃 张鉴铭.家用饮事暖煤炉热性能.制冷,2009,1(28):26-31.