期刊文献+

快速暂态过电压对断路器中并联电容的影响 被引量:11

Effect of Very Fast Transient Over-voltage on Shunted Capacitor in Circuit-breaker
下载PDF
导出
摘要 某550kVGIS中由于隔离开关操作故障,引起了断路器并联电容器爆炸。为找出该事故的原因,利用Fortran语言和MATLAB软件详细计算该电站GIS内部的快速暂态过电压(VFTO),分析了VFTO对断路器中并联电容的危害,并讨论了断路器中合闸电阻对VFTO的影响。结果表明,VFTO在双断口断路器的两个并联电容上的幅值有差异,并且在隔离开关操作过程中,并联电容上受到了热击穿的威胁,这也是造成此次事故的主要原因。同时研究结果还表明断路器中的合闸电阻可以抑制VFTO的幅值,缩小VFTO的频率范围。 In a 550 kV GIS, the shunt capacitor in circuit-breaker is exploded because of the fault of disconnector. In order to research the reason of this accident, the very fast transient over-voltage (VFTO) in 550 kV GIS was calculated using the FORTRAN language, and Matlab program and the effect of VFTO on shunt capacitors in the circuitbreaker was analyzed. Meanwhile, the influence of closing resistance in circuit breaker was discussed. It is indicated that the VFTO distribution in the shunt condenser of double-fracture circuit-breaker is different. The shunt condenser is also threatened by the thermal effect due to VFTO in the isolation switch operation. The VFTO can be inhibited by the closing resistance in the circuit-breaker.
出处 《高电压技术》 EI CAS CSCD 北大核心 2009年第10期2361-2365,共5页 High Voltage Engineering
基金 高等学校科技创新工程重大项目培育资金项目(707018)~~
关键词 全封闭气体绝缘变电站(GIS) 快速暂态过电压(VFTO) 断路器 并联电容 合闸电阻 隔离开关 GIS very fast transient over-voltage circuit-breaker shunted capacitor closing resistance disconnector
  • 相关文献

参考文献14

  • 1Povh D, Schmitt H, Volker O, et al. Modelling and analysis guidelines for very fast transients I J]. IEEE Transactions on Power Delivery, 1996, 11(4): 2028-2035.
  • 2Edlinger A, Mauthe G, Pinnekamp F, et al. disconnector switching of charging currents in metal-enclosed SF6-Gas insulated switchgear at EHV[C] //CIGRE Report. Paris, France: CIGRE, 1984:13-14.
  • 3Lin Xin, Tian Chi, Xu Jianyuan, et al. Comparison and analysis on very fast transient over voltage based on 550 kV GIS and 800 kV GIS[C]//2008 International Conference on High Voltage Engineering and Application. Chongqing, China:[s. n.], 2008: 288-291.
  • 4He Baina, Lin Xin. The research of high speed earthing switch on EHV[C]//2006 China International Conference on Electricity Distribution. Beijing, China: [s. n. ], 2006.
  • 5Meng Tao, Lin Xin, Xu Jianyuan. The effect of GIS apparatus parameter on very fast transient over-voltage[C]//2008 International Conference on High Voltage Engineering and Application. Chongqing, China: [s. n.]. 2008: 292-295.
  • 6林莘,司秉娥,徐建源,路璐.【特约】1100kV GIS中隔离开关及故障接地开关电场数值分析[J].沈阳工业大学学报,2007,29(5):524-528. 被引量:22
  • 7徐建源,司秉娥,林莘,路璐.基于虚拟介电常数法的特高压GIS中隔离开关电场参数计算[J].电工技术学报,2008,23(5):37-42. 被引量:29
  • 8谷定燮,修木洪,戴敏,周沛洪.1000kV GIS变电所VFTO特性研究[J].高电压技术,2007,33(11):27-32. 被引量:111
  • 9沈文琪.电力电容器的实际使用寿命与使用条件的关系[J].电力电容器,2004(1):27-28. 被引量:22
  • 10徐延献.高温介质损耗的测量与计算.电子元件与材料,1988,7(1):62-64.

二级参考文献36

共引文献186

同被引文献245

引证文献11

二级引证文献239

相关作者