110kV贵州剑牵线雷害事故分析及防雷措施的探讨 被引量:7

Analysis of the Lightning Strike Fault of 110 kV Jianqian Transmission Line in Guizhou and Lightning Protection Measures
下载PDF
导出
摘要 110 kV输电线路所经地多为山区,因其地势高,档距大,杆塔接地电阻超标等原因极易遭受雷击而发生雷击跳闸事故。笔者在具体调查了贵州110 kV剑牵输电线路遭受雷击后的雷击点状况和绝缘子闪络烧伤痕迹资料后,结合有关理论分析指出:雷电反击过电压和接地电阻严重超标是导致该线路经常跳闸的主要原因。结果表明:只有采取降低杆塔接地电阻、加装侧向避雷针、加强绝缘和加装均压环等措施才能有效减小雷击对该线路造成的损害。基于此分析结果,提出了几种减少高压输电线路雷击跳闸率的措施,对实际防雷工作具有一定的意义。 Most of 110 kV transmission lines are located in mountainous areas, so they are apt to be struck by lightning and suffer frequent tripping because of high lands, large tower span and excessive tower grounding resistance. The lightning strike points and the flashover marks of insulators of Guizhou 110 kV Jianqian transmission line was investigated and analyzed according to relevant theories, it was indicated that frequent tripping is mainly due to over-voltage lightning and seriously excessive tower grounding resistance. The result showed that in order to reduce damage caused by lightning strike on the transmission line, measures must be taken to reduce tower grounding resistance, enhance insulation level and install side lightning rods and grading rings. Based on the above analysis, several measures was proposed to reduce lightning trip-out rate of high voltage transmission lines, which have a certain significance to prevent lightning accidents.
出处 《电瓷避雷器》 CAS 北大核心 2009年第5期23-27,共5页 Insulators and Surge Arresters
关键词 110 KV输电线路 雷击 接地电阻 侧向避雷针 110 kV transmission line lightning strike tower grounding resistance side lightning rod
  • 相关文献

参考文献5

二级参考文献40

  • 1李景录,卢宣明,李丛旺,刘先进,胡毅.高效膨润土防腐降阻剂的开发研制[J].高电压技术,1994,20(4):61-63. 被引量:10
  • 2张艳梅,刘长树,王永勤.输电线路绝缘子污秽在线监测系统的应用[J].高电压技术,2006,32(3):112-114. 被引量:21
  • 3贺博,林辉.人工污秽试验中绝缘子泄漏电流的统计特性[J].高电压技术,2006,32(8):4-6. 被引量:15
  • 4.DL/TG20—1997.交流电气装置的过电压保护和绝缘配合[S].,..
  • 5.DL/TG21—1997.交流电气装置的接地[S].,..
  • 6.GB30169—92.电气装置安装工程接地装置施工及验收规范[S].,..
  • 7李景禄.实用电力接地[M].技术:中国电力出版社,..
  • 8Wang C X.Sources of insulator charging and the induced electric field enhancement in gas insulated substations[C].IEEE 5th International Conference on Conduction and Breakdown in Solid Dielectrics.Britain,1995:149-153.
  • 9Lindsey G P.Porcelain insulators for outdoor cable terminations improvements in pollution performance[C].The Institution of Electrical Engineers.London,Britain:IEE,1996:235-238.
  • 10Topalis F V,Gonos I F.Stathopulos A.Dielectric behaviour of polluted porcelain insulators[J].IEE Proc-Gener,Transm,Distrib,2001,148(4):269-274.

共引文献171

同被引文献28

引证文献7

二级引证文献96

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部