期刊文献+

新安江水电厂水轮机进相试验研究 被引量:3

Phase-advance test and research on turbines of Xin'anjiang hydropower plant
下载PDF
导出
摘要 水轮发电机适时进相运行,能改善和抑制电网电压水平。通过对新安江水力发电厂4号机进相试验研究,指出发电机静稳极限、厂用电电压、定子端部结构件温升是发电机进相运行的主要限制条件。进相试验确定低励限制的范围,提高水轮发电机的进相运行能力。 Timely phase-advance operation of turbine-generators can improve and suppress the grid voltage level. Through phase-advance test and research on No. 4 Unit of Xin'anjiang hydropower plant, it shows that the static stability limit of generator, service power voltage and temperature rise of stator end elements are the main constraints for phase-advance operation of generators. The phase-advance test can determine the range of low excitation limit and improve the phase-advance operation capability of turbine-generators.
出处 《西北水电》 2009年第5期57-60,共4页 Northwest Hydropower
关键词 发电机 进相试验 电压调节 试验研究 generator phase-advance test voltage regulation test research
  • 相关文献

参考文献2

  • 1章卫光,吴正良.新安江水电厂运行规程(QJ/11300041.05.014.01-2007)[Z].新安江:新安江电厂,2007.
  • 2李福兴,徐鹏.新安江水力发电厂1~9号发电机组进相试验[R].华东电力试验研究院有限公司,2008.

同被引文献12

  • 1DL/T751-2001水轮发电机运行规程[S].2002.
  • 2.电力系统电压和无功电力技术导则(试行)[S].[S].中华人民共和国能源部,1989..
  • 3DL/T 596-2005,电力设备预防性试验规程[S].北京:中国电力出版社,2005.
  • 4GB/T8564-2003,水轮发电机组安装技术规范[S].北京:中国标准出版社,2004.
  • 5JB/T6204-2002,高压交流电机定子线圈及绕组绝缘耐电压试验规范[S].北京:中国标准出版社,2003.
  • 6GB 50150-2006,电气装置安装工程电气设备交接试验标准[S].北京:中国计划出版社,2007.
  • 7SL600-2012,水轮发电机定子现场装配工艺导则[S].北京:中国水利水电出版社,2013.
  • 8GB 1985-2004,高压交流隔离开关和接地开关[S].北京:中国标准出版社,2004.
  • 9赵万明.李家峡水电站发电机3ω定子接地保护改进建议[J].西北水电,2010(2):66-68. 被引量:1
  • 10曹罡,杨卫锋,陈逊.构皮滩水电站水轮发电机进相能力分析[J].贵州水力发电,2010,24(2):36-40. 被引量:2