摘要
分析和计算了程控机房间接利用室外冷源的关键设备空气冷却器的热工特性。结果显示,空气冷却器填料厚度越大,总换热量越大;淋水初温越低,相同换热量下的填料厚度越小;冷水温度每降低1℃所能减小的填料厚度仅为5 cm,相比于提高冷水进口温度经济效益不明显,一般可确定13℃为冷水进口温度。
Analyses and calculates the thermal characteristics of the key equipment--air cooler for indirect free cooling tower used in communication rooms. The results show that the more stuffing height is, the more total heat exchange is, the less spray water temperature is, the less stuffing height is under the same heat exchange. When the temperature of cold water is decreased by 1 ℃, the stuffing height is decreased by merely 5 cm and it is not very significant compared with increased cold water temperature, and the inlet cold water temperature generally is determined as 13 ℃.
出处
《暖通空调》
北大核心
2009年第11期83-87,共5页
Heating Ventilating & Air Conditioning
基金
国家自然科学基金资助项目(编号:50578049)
"十一五"国家科技支撑计划资助课题(编号:2006BAJ01A09
2008BAJ12B05-05)
关键词
室外冷源
空气冷却器
规则纸填料
热工特性
outdoor cold source, air cooler, regular stuffing, thermal characteristic