期刊文献+

1100 kV GIS隔离开关分合容性小电流试验中的暂态电压测量 被引量:15

Transient Voltage Measurement in Switching Small Capacitive Current Test of 1 100 kV GIS Disconnector
下载PDF
导出
摘要 GIS隔离开关分合容性电流过程持续时间长,同时产生高幅值、大陡度、高频率的过电压。采用新研制的光纤式电压测量系统,对1 100 kV GIS隔离开关分合小电容电流试验中的暂态电压进行测量,得到了分合过程中负载电容上"台阶"状电压波形,同时采用EMTP仿真软件对电压波形进行相应的仿真研究,得到了负载上电压的幅值、频率、波形等相应特性。而且试验和仿真结果一致。证明该测量系统可以用于特高压隔离开关分合容性电流用暂态电压的测量。 The process of GIS disconnector switching small capacitive current lasted longer, meanwhile, high amplitude, steep and high frequency overvoltage is produced. Using newly developed optical voltage measuring system, to measure the transient voltage in switching small capacitive current test of 1 100 kV GIS disconnector, is introduced in this paper. "Step" shape voltage waveform on load capacitor during switching process is obtained. Based on EMTP Simulation Software, the voltage amplitude, frequency, waveform and other relevant load characteristics are obtained. Moreover, the test and the simulation results are consistent, which proved that the measuring system can be used for transient voltage measurement in ultra high voltage disconnector switching capacitive current.
出处 《高压电器》 CAS CSCD 北大核心 2009年第6期106-109,114,共5页 High Voltage Apparatus
关键词 隔离开关 快速暂态过电压 测量 disconnector very fast transient overvohage(VFTO) measurement
  • 相关文献

参考文献4

二级参考文献13

  • 1何善庆.GIS中的快速暂态现象[J].高压电器,1995,31(2):41-46. 被引量:52
  • 2尹晓芳 王秋生 等.《72.5kV及以上GIS隔离开关开合母线充电电流的要求’简介[J].标准化信息,2000,(3):27-30.
  • 3[1]张仁逾,陈昌渔,王昌长.高电压试验技术[M].北京:清华大学出版社,2003.
  • 4Working Group 33/13-09. Very fast transient phenomena associated with gas insulated substation[C]. CIGRE Report 33-13. Paris, 1988.
  • 5V Vinod Kumar. VFTO computation in a 420 kV GIS[C]. IEE Conference Publication 1 467. Eleventh ISH. London, UK,1999: 1319-1322.
  • 6J Grandl. Studies of very fast transients (VFT) in a 765 kV substation[C]. CIGRE Report 33-12. Paris, 1988.
  • 7R Witzmann. Fast Transients in gas insulated substations (GIS)-modeling of different GIS components [C]. Fifth ISH. Braunschweig, 1987: 12. 06.
  • 8G Ecklin, D Schlicht, A Plessl. Overvoltages in GIS caused by the operation of isolators [M]. Surges in High-Voltage Networks. [s. l.]: Edited by Klaus Ragaller, 1982: 115-129.
  • 9R Sun. A simplified method for the determination of the maximum overvoltage factor during disconnector operation in GIS [C]. Seventh ISH. Dresden, Germany, 1991: 83.06.
  • 10张婷,方志,陈陶陶,赵龙章.球形电场测量系统在高压测量领域中的应用[J].电测与仪表,2007,44(11):11-16. 被引量:24