期刊文献+

带并联电抗器的超高压输电线路自适应重合闸新判据 被引量:26

A New Criterion for Adaptive Single Pole Auto-reclosure of EHV Transmission Lines with Shunt Reactor Compensation
下载PDF
导出
摘要 对带并联电抗器线路发生瞬时性单相接地故障时跳开相的恢复电压特征进行了分析,应用拉普拉斯变换对恢复电压中的各种暂态分量进行了定量求解,从原理上揭示了恢复电压中衰减周期分量的产生原因。通过瞬时性故障与永久性故障时故障相端电压波形的对比,提出了识别永久性单相接地故障的跳开相端电压衰减周期分量幅值判据,并给出一种从跳开相端电压中提取低频衰减周期分量幅值的实用方法,该方法计算简单,判定迅速准确,且不受过渡电阻影响,可有效应用于带并联电抗器的超高压输电线路单相自适应重合闸故障性质的识别及重合时刻的选择。 Based on the research on characteristics of the recovery voltage of the opened phase when a transient single phase fault occurs on a shunt reactor compensated transmission line, quantitative analysis is performed on the transient components of the recovery voltage by s-domain analysis. The cause of the decaying periodic component of the recovery voltage is revealed. Based on the comparison between the wave form of the terminal voltage of the faulted phase of a transient fault and that of a permanent fault, a criterion for identifying the magnitude of the decaying periodic component of the terminal voltage on the opened phase caused by the permanent single-phase fault is proposed and a practical method for extracting the magnitude is presented. The method is simple and fast, and not subject to the influence of transition resistance. It can be applied to fault nature identification in an adaptive single pole auto-reclosure scheme for transmission lines with shunt reactor compensation and selection of proper reclosure time instance.
出处 《电力系统自动化》 EI CSCD 北大核心 2009年第23期48-54,共7页 Automation of Electric Power Systems
基金 国家自然科学基金资助项目(50477037 50607014) 天津市自然科学基金资助项目(08JCYBJC13500)~~
关键词 自适应重合闸 瞬时性故障 永久性故障 电容耦合电压 电磁耦合电压 衰减周期分量 并联电抗器 adaptive single pole auto-reclosure transient fault permanent fault capacitive coupling voltage inductive coupling voltage decaying periodic component shunt reactor
  • 相关文献

参考文献9

二级参考文献34

共引文献178

同被引文献231

引证文献26

二级引证文献166

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部