期刊文献+

高大净空场所火灾实体灭火试验研究 被引量:25

Research on the fire extinguishing experiment in big clear space
下载PDF
导出
摘要 在吊顶净高16 m的情况下以标准燃烧物进行试验,研究高大净空场所自动喷水灭火系统灭火效果。第一组采用快速响应喷头,点火120 s后火焰高度7.2 m,点火位置正上方喷头动作,喷头动作后温度降至约30℃,周围喷头未动作,洒水对控制火势影响较小。339 s开始相隔喷头动作,喷头出现跳跃开放现象。第二组采用标准响应型大水滴喷头,点火164 s后点火位置正上方喷头动作,仅动作了一只喷头。自动喷水灭火系统能有效控火,但不能灭火。火灾危险等级较高的场所不宜采用快速响应喷头。 The fire extinguishment experiment of normative comburant was done to research the effect of sprinkler system at big space in witch height is 16 m. The fast response sprinklers were used in experiment 1 and the height of fire is 7.2 m after 120 s. The sprinkler above the fire acted and the temperature of fire decline to 30 ℃. The sprinklers nearby didn't act so the control of fire is weak. The sprinkiers begin to act but not one by one after 339 s. The deluge sprinklers of normal response were used-in experiment 2 and only the sprinkler above the fire acted at 164 s after ignition. The experiments shows that the sprinkler system could control fire well but could not put out the fire. The location with high fire risk should not use the fast response sprinkler.
出处 《消防科学与技术》 CAS 北大核心 2009年第12期912-915,共4页 Fire Science and Technology
基金 国家"十一五"科技支撑计划项目(2006BAK06B03)
关键词 大空间建筑 火灾 自动喷水灭火系统 大水滴 喷头 快速响应早期抑制喷头 big space building fire sprinkler system deluge sprinkler fast response sprinkler
  • 相关文献

参考文献7

  • 1GB 50084-2001自动喷水灭火系统设计规范(2005年版)[S].
  • 2Soonil Nam. Actuation of sprinklers at high ceiling clearance faeilities [J]. Fire Safety Journal, 2004,39(7) :619-642.
  • 3Nam S, Braga A, Kung H C, et al. Fire protection for non-storage occupancies with high ceiling clearances [C]. 7th International Symposium on Fire Safety Science, June 2002 : 16 - 21.
  • 4公安部天津消防研究所.火灾增长分析的原则和方法[R].国家十五重点科技攻关项目专题四研究报告,2004.
  • 5宋波,杨丙杰.仓库设置自动喷水灭火系统的应用探讨[J].消防科学与技术,2008,27(7):526-529. 被引量:21
  • 6宋波,李毅,刘欣,田立伟,杨震铭.高架仓库实体火灾的实验研究[J].消防科学与技术,2009,28(4):155-157. 被引量:23
  • 7NFPA 13,Standard for the Installation of Sprinkler Systems[S].

二级参考文献6

  • 1Peter J Chicarello, Joan M A Troup, Ronald K Dean. Large-scale fire test evaluatiom of ESFR Automatic sprinkler [R]. technical report, J. I. OM2RS. RR/OMOJ7. RR 070, May 1986, Factory Mutual Research.
  • 2GB50084-2001,自动喷水灭火系统设计规范[S].2005年版.
  • 3NFPA 13,Standard for the installation of sprinkler systems[S].
  • 4BS EN12845: 2004, Fixed firefighting systerns-automalic sprinkler systems-design, installation and maintenance[S].
  • 5宋波,杨丙杰.仓库设置自动喷水灭火系统的应用探讨[J].消防科学与技术,2008,27(7):526-529. 被引量:21
  • 6翁兴德,李锋华.仓库火灾的特点及预防措施[J].商品储运与养护,2002,24(2):43-45. 被引量:3

共引文献112