西门子GIS母联控回断线异常分析 被引量:1

Abnormal Cases Analysis about Siemens Gis Bus Tie’s Control Circuit Disconnection
下载PDF
导出
摘要 西门子8DN9(GIS)汇控柜在双母线带专用母联开关接线方式下,当某间隔两把母线刀闸同时合上,母联开关发控制回路断线信号。正常的热倒母线操作前要求按顺序执行以下三个步骤:母差改为互联方式、母联开关改非自动、母线压变二次并列;正常倒母线操作在倒排间隔两把母线刀闸同时合上前,母联开关已经改为非自动状态,故发现不了联锁条件所引起的母联控制回路断线。文章对苏州陆慕变电站发生的母联2510控制回路断线异常进行了详细分析,根据分析结果,对西门子GIS母联控制回路提出了对策和建议。 Siemens 8DN9 (GIS) bus tie switch may result in bus tie control circuit disconnection condition of the hot changeover busbars. Before the normal heat bus operation requests according to the order to carry out following three steps: the bus differential motion protection changes the single bus way, the bus tie change nonautomatically, the phase voltage transformers changes Parallel low-voltage side.Before the normal bus operation inverted at the same time use the isolating switch, the bus tie already to change the non-automatic condition, therefore the discovery interconnection condition caused bus tie the control circuit disconnection.This paper analyzes the cases that the Abnormal about the bus tie 2510's control circuit disconnection of Suzhou Lumu Substration in detail. According to results of the analysis,The author puts forward countermeasures and suggestions for the Siemens GIS bus tie's control circuit.
机构地区 苏州供电公司
出处 《电子与封装》 2009年第12期34-36,共3页 Electronics & Packaging
关键词 母联开关 控回断线 对策和建议 bus tie switch control circuit disconnection countermeasures and suggestions