期刊文献+

220kV母线差动保护双位置继电器故障分析及解决

Reason and Solution to Not-reversing of 220 kV Two-position Relay
下载PDF
导出
摘要 针对三河发电有限责任公司长期以来存在的母联开关合闸后,出现交流断线报警信号,母线差动保护出口被闭锁这一问题,通过查阅和分析三河发电有限责任公司220 kV母线差动保护有关图纸和厂家资料,经过回路查线,校验继电器及试验录波和反复研究,确认了问题的根本原因,并制定了解决了方案,从而消除了由于设计问题(从动继电器使用不当)而存在的隐患。 The present paper aims to solve the long-existing problem in Sanhe Power Plant that when the bus-bar switch is closed, the warning signal will show that AC circuit breaks and Bus Differential Protection exit is blocked. After examining relevant blueprint and manufacturer material, back-checking the line and relay, as well as repeated experiment and recording, the researchers finally find out the fundamental cause and make out correspondent solutions, which eliminates the potential safety hazard due to the design problem.
出处 《电力科学与工程》 2009年第12期53-55,共3页 Electric Power Science and Engineering
关键词 母联开关 交流断线 双位置继电器 翻转 bus-bar switch AC circuit break two-position relay reverse
  • 相关文献

参考文献1

  • 1上海继电器厂PMH-150(RADSS/S)型母线差动保护原理说明书.

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;