期刊文献+

天然酯-普通纸(或热稳定纸)绝缘热老化特性 被引量:15

Insulation Thermal Aging Properties of Natural Ester Immersed Paper Comparing With That of Conventional and Thermally Upgraded Papers
下载PDF
导出
摘要 为研究新型绝缘油天然酯与两种绝缘纸组成的酯-纸绝缘热老化特性,将天然酯-普通纸和天然酯-热稳定纸绝缘试品,在90℃、110℃和130℃下进行了399d的热老化试验。结果表明:天然酯-纸绝缘中,相同老化条件下,热稳定纸聚合度和稳定聚合度都分别明显高于普通纸;通过热稳定纸中含有双氰胺的红外光谱分析,从官能团角度研究了热稳定纸抑制绝缘老化的两大机制。热稳定纸能吸附较多糠醛;对同一种酯-纸绝缘,糠醛仍可作为衡量变压器中酯-纸绝缘老化程度的参量;对不同绝缘纸的酯-纸绝缘,糠醛含量的差异不能表征它们之间绝缘纸老化程度的差异。研究了这两种不同酯-纸绝缘老化过程中,酯中微水含量变化规律的异同,从而建议使用天然酯的变压器,用热稳定纸作为与之匹配的固体绝缘材料,以利于酯在老化过程中保持较好绝缘性能。 In order to compare the properties of natural ester impregnated Kraft paper and thermally upgraded paper, sealed aging vessels containing copper, insulation paper (Kraft paper ano thermally upgraded paper), and natural ester were aged at 90℃, 110℃, and 130℃ 399 days. The results show that both degree of polymerization(DP) and leveling-off degree of polymerization (LODP) for thermally upgraded paper were higher than the ones of Kraft paper at the same aging condition. The infrared spectrum evidence was given that there was dicyandiamide in thermally upgraded paper, and the aging resistance mechanisms of thermally upgraded paper were analyzed. Furfural can be absorbed by thermally upgraded paper and can be used to monitor the aging condition of a certain natural ester impregnated paper insulation. However, furfural can not be used to compare the aging condition of different types of paper immersed in natural ester. The different disciplinarians of the water content in natural ester were analyzed and the suggestion is given that the thermally upgraded paper are more suitable for natural ester impregnated paper insulation.
出处 《电工技术学报》 EI CSCD 北大核心 2009年第12期12-17,共6页 Transactions of China Electrotechnical Society
基金 国家重点基础研究发展计划项目(973项目)(2009CB724501-1) 国家自然科学基金(50677073) 国家杰出青年科学基金(50425722)资助项目
关键词 变压器 绝缘 老化 天然酯 热稳定纸 聚合度 Transformer insulation aging natural ester thermally upgraded paper degree of polymerization
  • 相关文献

参考文献20

  • 1Saha J K, Darreniza M, Hill D J T. Investigating the effects of oxidation and thermal degradation on electrical and chemical properties of power transformers insulation[J]. IEEE Transactions on Power Delivery, 1999, 14(4): 1359-1367.
  • 2杨丽君,廖瑞金,孙会刚,孙才新,李剑.油纸绝缘热老化特性及生成物的对比分析[J].中国电机工程学报,2008,28(22):53-58. 被引量:89
  • 3廖瑞金,冯运,杨丽君,向彬,刘刚.油纸绝缘老化特征产物生成速率研究[J].中国电机工程学报,2008,28(10):142-147. 被引量:87
  • 4廖瑞金,杨丽君,孙才新,李剑.基于局部放电主成分因子向量的油纸绝缘老化状态统计分析[J].中国电机工程学报,2006,26(14):114-119. 被引量:79
  • 5Boss P, Oommen T V transformers based on New insulating fluids for biodegradable high oleic vegetable oil and ester fluid[C]. IEE Colloquium on Insulating Liquids, London, 1999.
  • 6Oommen T V. Vegetable oils for liquid filled transformers[J]. IEEE Electrical Insulation Magazine, 2002, 18(1): 6-11.
  • 7李晓虎,李剑,杜林,杨丽君,孙才新.一种转基因菜籽绝缘油的电气性能[J].中国电机工程学报,2006,26(15):95-99. 被引量:41
  • 8Badent R, Hemmer M, Schwab A J. Inhibited rape-seed oil as substitute for mineral oils[C] Conference on Electrical Insulation and Dielectric Phenomena, Quintana Roo, Mexico, 2002.
  • 9Hemmer M, Badent R, Leibfriend T. Investigation of the suitability of commercially available bio-oils as insulating liquid[C]. Annual Report Conference on Electrical Insulation and Dielectric Phenomena, Virginia, 2003.
  • 10Hemmer M, BadenT R, Schwab A J. Electrical properties of rape seed oil[C]. Annual Report Conference on Electrical Insulation and Dielectric Phenomena, Virginia, 2003.

二级参考文献76

共引文献269

同被引文献215

  • 1刘文山,何冰,郑晓光.变压器油中糠醛含量与固体绝缘老化关系的研究[J].广东电力,2006,19(3):14-17. 被引量:12
  • 2廖瑞金,杨丽君,孙才新,李剑.基于局部放电主成分因子向量的油纸绝缘老化状态统计分析[J].中国电机工程学报,2006,26(14):114-119. 被引量:79
  • 3孙目珍.电介质物理[M].广州:华南理工大学出版社,2000:23,115-122.
  • 4Sans J R, Bilgin K M, survey of furanic Joseph J Kelly. Large scale compounds in operating transformers and implications for estimating service life[C]. 1998 IEEE International Symposium on Electrical Insulation, Arlington, USA, 1998: 543-553.
  • 5Hill D J T, Le T T, Darveniza M, et al. A study of degradation of cellulosic insulation materials in a power transformer, part 2: Tensile strength of cellulose insulation paper[J]. Polymer Degradation and Stability, 1995, 49: 429-435.
  • 6Kuang Y C, Chen G, Jarmm P. Recovery voltage measurement on oil-paper insulation with Simple geometry and controlled environment [C]. Proceedings of the 2004 IEEE International Conference on Solid Dielectrics, Toulouse, France, 2004, 2: 739-742.
  • 7Saha T K, Purkait P. Investigation of polarization and depolarization assessment of current measurements oil-paper insulation for the of aged transformers[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2004, 11 (1): 144-154.
  • 8Farahani M, Borsi H, Gockenbach E. Dielectric response studies on insulating system of high voltage rotating machines[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2006, 13(1): 383-393.
  • 9Yew J H, Pradhan M K, Saha T K. Effects of moisture and temperature on the frequency domain spectroscopy analysis of power transformer insulation[C]. IEEE Power Engineering Society General Meeting, Pittsburgh, USA, 2008: 1-8.
  • 10Ekanayake C, Gubanski S M, Graczkowski A, et al. Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation[J]. IEEE Transactions on Power Delivery, 2006, 21(3): 1309-1317.

引证文献15

二级引证文献192

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部