期刊文献+

过速140% Ne回路联片在发电机组保护中的应用 被引量:1

The Application of the Metal Connection Circuit of the Over-speed 140% Ne in the Protection of Water Turbine-generator
下载PDF
导出
摘要 黄河公伯峡水电站监控系统机组过速140%NePLC程序及控制回路设计不合理,给机组埋下了紧急停机、快速闸门落等严重事故隐患。为了防止重大事故,通过加装过速140%Ne联片等处理方法,消除安全隐患。改造后,当机组过速140%Ne误动时,未造成机组紧急事故停机流程动作,保证了机组安全运行。 The computer supervisory control system of Gongboxia power station has an illogicality in the PLC program and the control circuit of the over-speed 140%Ne of the sets,it could cause the generator emergency shutdown or the stop gate closed. In order to avoid the rotating speed runaway,install the over-speed 140%Ne metal connection in the circuit of generator emergency shutdown and the circuit of PLC generator emergency shutdown. After the reform,when the over-speed 140%Ne of the sets acting mistakely, the process of generator emergency shutdown won't work,make sure the security of people and equipment and the stability of the sets.
作者 张龙 李轶瑾
出处 《电力学报》 2009年第6期529-531,共3页 Journal of Electric Power
关键词 水轮发电机机组 过速140%Ne 联片 保护 water turbine-generator generator over-speedl40 % Ne metal connection protection