摘要
目前煤矿供电系统中,适用于中性点经消弧线圈接地的选择性漏电保护较少,针对该现状,文章在研究供电系统谐波理论的基础上,提出了应用五次谐波判断故障线路的理论。通过分析得出,故障线路与非故障线路中五次谐波电流方向相反且幅值最大,该结论可用于选择性漏电保护中。
At present there are few selective leakage protection applicable to the mine power system which neutral point is grounded by arc suppression coil. Aiming at this situation, based of the study of power system harmonies, the theory of application fifth harmonic on leakage protection was put forward. By analysis, compare to the fifth harmonics current in non - faulty line, the current in faulty line is in the opposite direction and is the maximum value. This conclusion can be used in selective leakage protection.
出处
《煤炭技术》
CAS
北大核心
2010年第1期40-42,共3页
Coal Technology
基金
山东省自然科学基金(Y2007G22)
关键词
谐波
消弧线圈接地系统
选择性
漏电保护
harmonics
arc suppression coil
selectivity
leakage protection