期刊文献+

北方地区浅埋人防工程热负荷特点 被引量:3

Numerical investigation of cooling(heating) load characteristics for shallow buried underground construction located in northern area of China
下载PDF
导出
摘要 为提高北方地区浅埋人防工程空调系统设计计算精度,以动态负荷的观点,探讨该类型工程的热负荷特征。采用统计方法分析了北方4城市(哈尔滨、长春、沈阳和北京)的典型气象年参数。以位于沈阳的某人防工程为例,运用二维数学模型计算了工程围护结构全年8 760 h的逐时传热量。计算过程中首先模拟计算了周围岩土层的温度,以该结果作为围护结构传热量计算的初始条件。热负荷的其他组成项中,假定人员和设备负荷为静态值,新风负荷则进行了动态计算。计算结果表明,北方地区浅埋型地下工程热负荷受工程外气象参数变化影响,也呈现出年周期性波动和日周期性波动。 To improve the accuracy of load calculation, the cooling (heating) load characteristics of shallow buried underground construction located in northern area of China were investigated in the perspective of dynamic load. The 'epw' form TMY data of 4 cities (Harbin, Changchun, Shenyang, and Beijing) were analyzed by statistics to understand the main meteorological features of northern China. A 2-dimensional mathematic model was built to simulate the year-round heat transfer process. The hour-by-hour numeric solutions of the 4 cities' ground temperature in different depths were generated by finite element method software, while the surface temperature as boundary condition was TMY data. The results were applied as the initial condition for the calculation of heat transfer quantities with the enclosure of underground building. In the case located in Shenyang city, the dynamic fresh air load was also calculated. However, for convenience in the discussion, the internal heat gain from light, people and equipments was set to static. The calculation result shows the periodic fluctuation characteristics of the load.
出处 《解放军理工大学学报(自然科学版)》 EI 北大核心 2009年第B12期64-68,共5页 Journal of PLA University of Science and Technology(Natural Science Edition)
关键词 逐时热负荷 浅埋工程 北方地区 周期性波动 hourly cooling (heating) load shallow buried underground construction northern area periodic fluctuation
  • 相关文献

参考文献7

  • 1中国建筑科学研究院.民用建筑热工设计规范GB57016-1993[S].北京:中国计划出版社,1993.
  • 2刘文杰.北方地区防护工程热湿环境分析与计算[D].南京:解放军理工大学,2006.
  • 3国家人民防空办公室.GB 50038-2005 人民防空地下室设计规范[S].北京:中国建筑标准设计研究院,2005
  • 4MAREF W, SWINTON M C, KENMARE M K, et al. Three-dimensional analysis of thermal resistance of exterior basement insulation systems (EIBS)[J]. Building and Environment, 2001 (36) : 407-419.
  • 5袁艳平,程宝义,茅靳丰.浅埋工程围护结构传热简化模型误差的有限元分析[J].制冷空调与电力机械,2003,24(6):10-12. 被引量:4
  • 6袁艳平,程宝义,茅靳丰.浅埋工程围护结构传热影响因素的有限元分析[J].洁净与空调技术,2004(2):35-37. 被引量:3
  • 7YUAN Yan-ping, DU Yan-xia. Semi-analytical solution for steady-periodic heat transfer of attached underground engineering envelope [J]. Building and En- vironment, 2008(43) : 1147-1152.

二级参考文献5

共引文献27

同被引文献51

引证文献3

二级引证文献17

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部