期刊文献+

过渡电阻对故障暂态分量的影响分析 被引量:16

Impact of fault resistance for fault transient component
下载PDF
导出
摘要 线路故障后产生大量的暂态分量,会影响常规保护的动作性能。利用分布参数等值超高压长距离输电线路,重点分析了过渡电阻对暂态高频分量的影响,分别讨论了相间短路和接地故障时,暂态高频分量与过渡电阻之间的关系。理论分析表明:故障暂态高频分量在频域上表现为一系列固有频率的形式,固有频率受过渡电阻的影响,固有频率的衰减系数与过渡电阻成反比,接地故障时,暂态高频分量中频率最低者与过渡电阻无关,只与电源侧反射系数和线路长度有关。利用PSCAD进行了仿真验证,仿真结果与理论分析相符。 The transient component generated by faults of transmission line affects the performance of protection. Distributed parameter model is used to express EHV transmission lines and impact of fault resistance for transient component is analyzed. The relation between transient component and fault resistance is discussed. Theory analysis shows that the fault component is a series of natural frequencies in frequency domain, when grounding fault occurred, the lowest one of natural frequencies does not impact by fault resistance and the attenuation coefficient increase with fault resistance. Simulation is carried out on PSCAD system with 1000kV power system.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2010年第2期18-21,共4页 Power System Protection and Control
关键词 继电保护 过渡电阻 暂态分量 固有频率 relay protection: fault resistance: transient component: nature frequency
  • 相关文献

参考文献4

  • 1斯拉麦卡E,瓦特西W.高低压电网中的暂态过程计算原理[M].程积高,译.北京:机械工业出版社,1983.
  • 2唐勇,陈珩,戴方涛,江世芳.行波保护研究中输电线路模型的选择[J].中国电机工程学报,1997,17(4):269-273. 被引量:23
  • 3Giovanni Miano. Transmission Lines and Lumped Circuits [M]. San Diego: USAAcademicPress, 2001.
  • 4Swift G W. The Spectra of Fault Induced Transient[J]. IEEE Trans on Power Apparatus and Systems, 1979,98(3).

二级参考文献1

  • 1Zhang X P,Electr Power Energy Syst,1995年,17卷,4期,239页

共引文献23

同被引文献194

引证文献16

二级引证文献138