数据通信机房空调通风系统的实验测试分析 被引量:13

Experimental Tests on Air-conditioning Ventilation of Data Communication Equipment Room
下载PDF
导出
摘要 数据通信设备的高度集成化,使得单机设备发热量不断增大,机房空调系统单位面积能耗急剧增大,针对数据通信机房中空调上送风侧回风气流组织方式下的数据通信设备的空调冷却效果进行试验测试,分析了其冷却效果差的原因,摸清了现有通风冷却方式存在的主要问题,并对其提出了相应的改进措施。 With the data communication equipment integrated highly, the refusing heat of stand-alone communication equipment is being increased dramatically. Meanwhile, the energy consumption per unit area of air-conditioning system for the communication room is increased dramatically. By experiment, the cooling effect of air-conditioning system under the upward air supply side return airflow organization model is tested and valued and some conclusions are derived by the analyzed results. The reasons for low cooling efficiency and the main problems of the existing ventilation cooling mode are analyzed on the experimental data, and some advice to improve the cooling effect of airconditioning srstem are proposed.
出处 《建筑节能》 CAS 2010年第2期29-31,共3页 BUILDING ENERGY EFFICIENCY
关键词 通信机房 空调 气流组织 实验 communication equipment room air-conditioning air distribution experiment