期刊文献+

工质对平板型LHP运行特性影响的实验研究 被引量:6

EXPERIMENTAL STUDY OF EFFECTS OF OPERATING CHARACTERISTICS FOR A FLAT-TYPE LOOP HEAT PIPE WITH DIFFERENT WORKING FLUID
原文传递
导出
摘要 本文研制了一套以不锈钢丝网为毛细芯的平板式蒸发器、风冷管翅式冷凝器的环路热管,并着重研究其以甲醇和丙酮为工质时运行特性的差异。实验结果表明,小型平板式LHP具有良好的启动特性和适应变热负荷能力,在相同的工况条件下,以丙酮为工质的LHP温度波动较小,系统启动较快且蒸发器壁面温度较低,但其极限热负荷能力低于甲醇。 This paper developed a set of loop heat pipe, which is made up of evaporator with stainless steel porous wick, and fin-tube condenser, and the effects of working fluid of methanol and acetone to the LHP operation characteristics are studied. Experimental results present that the small LHP shows excellent startup reliability and work capability, under the same working condition, the LHP with acetone as working fluid show a lower temperature oscillation amplitude and quicker startup timer and lower evaporator wall temperature, but the heat load linfits is smaller than LHP with methanol as working fluid.
出处 《工程热物理学报》 EI CAS CSCD 北大核心 2010年第3期487-490,共4页 Journal of Engineering Thermophysics
基金 国家自然科学基金项目(No.50876035 No.50906025) 中国博士点基金新教师项目(No.20070487093)
关键词 环路热管(LHP) 工质 温度波动 实验研究 loop heat pipe (LHP) working fluid temperature oscillation experimental investigation
  • 相关文献

参考文献12

  • 1Maydanik Yu F. Loop Heat Pipes [J]. Appl. Therm. Eng., 2005, 25(5/6): 635-657.
  • 2Launay S, Sartre V and Bonjour J. Parametric Analysis of Loop Heat Pipe Operation: a Literature Review [J]. Int. J. Therm. Sci, 2007, 46(7): 621-636.
  • 3LIU Zhichun, LIU Wei, Nakayama A. Flow and Heat Transfer Analysis in Porous Wick of CPL Evaporator Based on Field Synergy Principle [J]. Heat Mass Transfer, 2007, 43(12): 1273-1281.
  • 4Randeep S, Aliakbar A and Masataka M. Operational Characteristics of a Miniature Loop Heat Pipe with Flat Evaporator [J]. Int. J. Therm. Sci., 2008, 47(11): 1504-1515.
  • 5Boo J H, Chung W B. Thermal Performance of a Small- Scale Loop Heat Pipe with PP Wick [C]//13^th IHPC. Shanghai, 2004:259-264.
  • 6Roger R Riehl, Thiago Dutra. Development of an Experimental Loop Heat Pipe for Application in Future Space Missions [J]. Appl. Therm. Eng., 2005, 25(1): 101-112.
  • 7Lee W H, Park K H, Lee K ,J. Study on Working Characteristics of Loop Heat Pipe Using a Sintered Metal Wick [C]//13^th IHPC. Shanghai, 2004:265-269.
  • 8张红星,林贵平,丁汀,邵兴国,R.G.Sudakov,Y.F.Maidanik.环路热管启动特性的实验研究[J].中国科学(E辑),2005,35(1):17-30. 被引量:26
  • 9Chen Y M, Groll M, Mertz R. Steady-State and Transient Performance of a Miniature Loop Heat Pipe [J]. Int. J. Therm. Sci., 2006, 45(11): 1084 -1090.
  • 10柏立战,林贵平,张红星.重力辅助环路热管稳态运行特性的实验研究[J].航空学报,2008,29(5):1112-1117. 被引量:14

二级参考文献14

  • 1Ku J T. Operating characteristics of loop heat pipes. Society of Automotive Engineers. Paper No 1999-01-2007, 1999.
  • 2Maidanik Y F, Solodovnik N N, Fershtater Y G Investigation of dynamic and stationary characteristics of a loop heat pipe. IX International Heat Pipe Conference, Albuquerque, New Mexico, 1995.
  • 3Ku J T, Ottenstein L, Kaya T, et al. Testing of a loop heat pipe subjected to variable accelerating forces,Part 1: Start-up. Society of Automotive Engineers. Paper No 2000-01-2489, 2000.
  • 4Cheung K H, Hoang T, Ku J T, et al. Thermal performance and operational characteristics of loop heat pipe(NRL LHP). Society of Automotive Engineers. Paper No 981813, 1998.
  • 5Baumann J, Cullimore B, Yendier B, et al. Non-condensable gas, mass, and adverse tilt effects on the start-up of loop heat pipes. Society of Automotive Engineers. Paper No 1999-01-2048, 1999.
  • 6Baumann J, Cullimore B, Ambrose J, et al. A methodology for enveloping reliable start-up of LHPs.American Institute of Aeronautics and Astronautics. Paper No A00-33681, 2000.
  • 7Chuang P A, Cimbala J M, Conroy C T, et al. Comparison of experiments and 1-D steady-state model of a loop heat pipe[C]//Proceedings of IMECE. Paper No. 2002-33542, 2002.
  • 8Ku J T. Operating characteristics of loop heat pipes[R]. Society of Automotive Engineers, Paper No. 1999-01- 2007, 1999.
  • 9Parker M L. Modeling of loop heat pipe with applications to spacecraft thermal control[D]. Pennsylvania: University of Pennsylvania, 2000.
  • 10Meyer R, Muller R, Beckmann K, et al. Investigation of the heat transfer performance of a capillary pumped ammonia loop under gravity[R]. Society of Automotive Engineers, Paper No. 932304, 1993.

共引文献33