期刊文献+

北京地区温室地源热泵供暖能耗及经济性分析 被引量:56

Energy consumption and economic analysis of ground source heat pump used in greenhouse in Beijing
下载PDF
导出
摘要 为研究地热在温室中应用的可行性,该文在北京地区一栋日光温室中采用地下水式地源热泵系统进行了供暖试验研究。试验结果表明,整个供暖期(2007年10月15日-2008年3月10日)地源热泵系统的供暖性能系数约为3.83,与燃煤热水采暖系统相比,地源热泵系统供暖可节约42%的能源消耗量,具有显著的节能减排效果。温室内单位面积的每日供暖耗电量约为0.15kW·h/(m2·d),供暖费用约为0.12元/(m2·d)。地源热泵供暖、天然气供暖、燃煤热水供暖以及燃油热风供暖几种温室采暖方式的相对运行费用分别约为1.20、1.31、1.00与3.36,地源热泵供暖的运行费用略高于燃煤热水供暖,但低于天然气供暖和燃油热风供暖。 In order to study the feasibility of the application of ground source heat pump(GSHP) in greenhouses,experimental research on groundwater-style ground source heat pump system was carried out in greenhouse heating in Beijing. Experimental result showed that the coefficient of the system performance in greenhouse heating had reached 3.83 during the heating period of Oct.15,2007-Mar.10,2008,about 42% energy had been saved compare with conventional coal-fired hot water heating system,which its merits of energy-saving and greenhouse gases mitigating of the system were distinctive. The total electric consumption and the heating cost of the system was 0.15 kW·h/(m^2·d) and 0.12 Yuan/(m^2·d) ,respectively. The comparison among the heating systems of GSHP,natural gas,coal and light diesel oil were made,which the relative heating cost were 1.20,1.31,1.00 and 3.36,respectively,and the heating cost of ground source heat pump was higher than that of coal slightly,but was lower than that of natural gas and light diesel oil apparently.
出处 《农业工程学报》 EI CAS CSCD 北大核心 2010年第3期249-254,共6页 Transactions of the Chinese Society of Agricultural Engineering
基金 "十一五"国家科技支撑计划现代高效设施农业工程技术研究与示范课题(2006BAD28B07) 资源节约关键技术标准研制课题(2006BAK04A03)
关键词 温室 供暖 经济性分析 能耗 地源热泵 greenhouses heating economic analysis energy dissipation ground source heat pump
  • 相关文献

参考文献13

  • 1Michopoulos A.Three-years operation experience of a ground source heat pump system in Northern Greece[J].Energy and Buildings,2007,39 (4):328-334.
  • 2Karlsson F,Fahlén P.Capacity–controlled ground source heat pumps in hydronic heating systems[J].International Journal of Refrigeration,2007,30 (2):221-229.
  • 3Zheng D.Modeling of Standing Column Well in Ground Source Heat Pump System[D].Stillwater:Oklahoma State University,2004.
  • 4马最良 姚杨.水环热泵空调系统设计[M].北京:化学工业出版社,2005..
  • 5Kozai T.Thermal performance of an oil engine driven heat pump for greenhouse heating[J].Journal of Agricultural Engineering Research,1986,35(1):25-37.
  • 6Ozgener O,Hepbasli A.A parametrical study on the energetic and exergetic assessment of a solar-assisted vertical ground-source heat pump system used for heating a greenhouse[J].Building and Environment,2007,42(1):11-24.
  • 7方慧,杨其长,孙骥.地源热泵-地板散热系统在温室冬季供暖中的应用[J].农业工程学报,2008,24(12):145-149. 被引量:34
  • 8柴立龙,马承伟,张晓蕙,曲梅,陈青云,余飞.地源热泵温室降温系统的试验研究与性能分析[J].农业工程学报,2008,24(12):150-154. 被引量:34
  • 9吴荣华,张承虎,李桂涛,孙德兴,任南琪.地表水源热泵系统节能系数及环境影响研究[J].太阳能学报,2007,28(7):751-755. 被引量:12
  • 10胡兴岩,刘雪玲.热泵供暖的经济性分析[J].地热能,2005(1):22-24. 被引量:5

二级参考文献46

共引文献106

同被引文献681

引证文献56

二级引证文献374

相关作者