针对桥巩水电站三次谐波3W定子接地保护在机组空载状态下无法实现保护功能的问题,提出了通过在保护回路的接线中增加发电机出口开关的位置接点,使接地保护更加准确、可靠。
Qiaogong Hydropower Station had ever seen the third harmonic 3W generator stator earthing protection fails to work under no-load condition. In view of this problem, additional position contacts of generator terminal switchgear are designed in the protection circuit, so as to acquire more correct and reliable protection.
出处
《广西水利水电》
2010年第2期40-42,共3页
Guangxi Water Resources & Hydropower Engineering
关键词
灯泡惯流式发电机组
三次谐波
3W
定子接地保护
桥巩水电站
Bulb turbine generator unit
third harmonic
3W
stator earthing protection
Qiaogong Hydropower Station