110kV双回线与其他线路在部分同塔情况下的跳闸分析 被引量:6

Trip-out analysis of 110 kV double-circuit transmission lines and other lines partly on same tower
下载PDF
导出
摘要 介绍了某线路与110 kV双回线中的一条部分同塔的情况下,当该线路发生故障时,由于零序互感及双回线闭合环网的同时存在致使双回线某侧开关误跳闸的相关情况。根据各侧保护动作情况和事故录波进行分析,剖析了事故原因。简要计算了在大小方式下可能让保护误动的零序电流的大小。针对双回线并列运行且与其他线路部分同塔情况下导致保护装置误动的问题,提出在运行中运行方式的优化以及电网规划时对保护配置的要求,为同类问题的解决提供了参考。 Trip-out analysis of the circuit breaker and correlation aspects of 110 kV double-circuit lines is decribed in the paper. When short-circuit fault happened, the coexistance of zero-sequence mutual inductance and double-circuit ring netwOrk may lead to breaker trip-out. The malfunction cause is analyzed according to the relay protection and fault wave recording. The zero-sequence currents of protection is calculated in large and small mode, respectively. Considering double-circuit lines and other lines on one tower may leading to protection misoperation, optimization of operating mode and requirement of relay protection allocation in power grid planning are proposed in the paper, providing reference for the same design.
机构地区 德阳电业局
出处 《电力系统保护与控制》 EI CSCD 北大核心 2010年第9期80-83,共4页 Power System Protection and Control
关键词 同塔 零序互感 零序电流 跳闸分析 环网 误动 优化 same tower zero-sequence mutual-inductance zero-sequence current trip-out analysis ring network misoperation optimization
  • 相关文献

参考文献4

  • 1DL400-91.继电保护和安全自动装置技术规程[S].[S].,..
  • 2国家电力调度通信中心.电力系统继电保护实用技术问答(第二版)[M].北京:中国电力出版社,1999..
  • 3The National Dispatching Communication Centre. Practical Q & A for Power System Protection, Second Edition [M]. Beijing: China Electric Power Press, 1999.
  • 4刘万顺.电力系统故障分析[M].北京:中国电力出版社,2006:25-75.

共引文献32

同被引文献37

引证文献6

二级引证文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部