期刊文献+

基于同步相量测量的N端输电线路故障测距新算法 被引量:16

A New Fault Location Algorithm for N-Terminal Transmission Lines Based on Synchronized Phasor Measurement
下载PDF
导出
摘要 鉴于现有多端故障测距方法存在的缺陷,诸如采用未能真实反映实际情况的线路集中参数模型,在T节点附近高阻短路故障时有测距死区,算法过于复杂不易实现,受系统运行方式的影响等,在T节点附近发生高阻短路故障时,无法正确判别故障支路。针对该缺陷,提出一种N端输电线路同步故障测距新算法。首先,由离参考端最远的母线推算离参考端最近的T节点的电压、电流,在该T节点和参考端之间利用双端测距算法求出故障距离;基于该故障距离的分布特点将原N端输电线路的故障测距问题转化为一个T型线路的故障测距问题。然后,提出一种T型输电线路故障测距新算法。该方法无测距死区,克服了传统方法在T节点附近有测距死区的不足,测距精度受过渡电阻、故障类型和负荷电流的影响很小。EMTDC仿真结果表明新算法正确,具有很高的测距精度。 Due to the defects of existing synchronized phasor measurement (SPM) based fault location methods for multi-terminal transmission lines, such as the adopted lumped parameter models of transmission line cannot reflect correctly actual condition, there is dead zone of fault location while the high resistance fault occurred near the teed node, or the algorithm is too complex to implement, the adopted algorithms are affected by operation modes of power system, etc., the faulty branch cannot be correctly judged when high resistance fault occurred near the teed node. For this reason, in this paper a new fault location algorithm for multi-terminal transmission lines using SPM is proposed. Firstly, the voltage and current of the teed node that is the nearest to the reference bus are calculated by the voltage and current data of the bus that is the farthest to the reference bus, and by use of two-terminal fault location algorithm the fault location between the teed node and reference bus is solved; then based on the distribution characteristic of this fault location, the fault location problem of original N-terminal transmission lines is changed into the fault location of a teed transmission line; finally, a new fault location algorithm without dead zone for teed transmission line is given. The given algorithm remedies the defect of traditional fault location methods in which dead zone of fault location exist. The accuracy of the given algorithm is slightly affected by transition resistance, fault types and load current. The results of simulation by EMTDC show that the proposed new algorithm is correct and can locate the faults accurately.
出处 《电网技术》 EI CSCD 北大核心 2010年第5期154-160,共7页 Power System Technology
基金 国家自然科学基金重点项目(50837002)~~
关键词 多端输电线路 T型线路 故障测距函数:相位特性 测距死区 同步相量测量 multi-terminal transmission lines teed line fault location function phase characteristics dead zone of faultlocation synchronized phasor measurement
  • 相关文献

参考文献16

  • 1束洪春,高峰,陈学允,许承斌.T型输电系统故障测距算法研究[J].中国电机工程学报,1998,18(6):416-420. 被引量:64
  • 2束洪春,陈学允,许承斌.多端辐射状输电线路故障测距的一种实用算法[J].电力系统自动化,1998,22(2):21-25. 被引量:8
  • 3Abe M, Otsuzuki N, Emura T, et al. Development of a new fault location system for multi-terminal single transmission line[J]. IEEE TransonPowerDelivcry, 1995, 10(1): 159-168.
  • 4Nagasawa T, Abe M, Otsuzuki N, et al. Development of a new fault location algorithm for multi-terminal two parallel transmission lines [J]. IEEE Trans on Power Delivery, 1992, 7(3): 1516-1532.
  • 5Funabashi T, Otoguro H, Mizuma Y, et al. Digital fault location algorithm for parallel double-circuit multi-terminal transmission lines[J]. IEEE Trans on Power Delivery, 2000, 15(2): 531-537.
  • 6Sanderson J V R, Santana R G R, A1Fakri B. Improved directional comparison based algorithm for protection of multi-terminal transmission lines[C]. Fifth International Conference on Developments in Power System Protection, 1993: 153-156.
  • 7Brahma S M. New fault location method for a single multi-terminal transmission line using synchronized phasor measurements[J]. IEEE Trans on Power Delivery, 2006, 21(3): 1148-1153.
  • 8Liu C W, Lien K P, Chen C S, et al. A universal fault location technique for N-terminal (N > 3) transmission lines[J]. IEEE Trans on Power Delivery, 2008, 23(3): 1366-1373.
  • 9Chen C S, Liu C W, Jiang J A. Three-terminal transmission line protection using synchronized voltage and current phasor measurements[C]. IEEE/PES Asia Pacific Transmission and Distribution Conference and Exhibition, 2002.
  • 10Lien K P, Liu C W, Jiang J A, et al. A novel fault location algorithm for multi-terminal lines using phasor measurement units[C]. IEEE Power Symposium, Proceedings of the 37th Annual North American, Ames, USA, 2005.

二级参考文献19

  • 1李胜芳,范春菊,郁惟镛.T型支接线路的自适应故障测距算法[J].电工技术学报,2004,19(10):59-64. 被引量:41
  • 2康小宁,索南加乐.基于参数识别的单端电气量频域法故障测距原理[J].中国电机工程学报,2005,25(2):22-27. 被引量:51
  • 3董新洲,葛耀中.一种使用两端电气量的高压输电线路故障测距算法[J].电力系统自动化,1995,19(8):47-53. 被引量:80
  • 4胡帆,刘沛,程时杰.高压输电线路故障测距算法仿真研究[J].中国电机工程学报,1995,15(1):67-72. 被引量:60
  • 5Girgis A A, Hart D G, Peterson W L. A new fault location technique for two- and three-terminal lines[J]. IEEE Trans on Power Delivery, 1992, 7(1): 98-107.
  • 6Kalam A, Johns A T. Accurate fault location technique for multi-terminal EHV lines[C]. IEE international Conference on Advances in Power System Control, Operation and Management, Hong Kong, 1991.
  • 7Nagasawa T, Abe M, Otsuzuki N, et al. Development of a new fault location algorithm for multi-terminal two parallel transmission lines [J]. IEEE Transon Power Delivery, 1992, 7(3): 1516-1532.
  • 8Abe M, Otsuzuki N, Emura T, et al. Development of a new fault location system for multi-terminal single transmission lines[J], IEEE Trans on Power Delivery, 1995, 10(1): 159-168.
  • 9Gong Qingwu, Chen Yunping, Zhang Chengxue, et al. A study of the accurate fault location system for transmission line using multi-terminal signals[C]. IEEE Power Engineering Society Winter Meeting, Columbus, Ohio, USA, 2000.
  • 10Tziouvaras DA, Roberts J B, Benmouyal G. New multi-ended fault location design for two- or three-terminal lines[C]. IEE Conference on Developments in Power System Protection, Amsterdam, Netherlands, 2001.

共引文献100

同被引文献258

引证文献16

二级引证文献209

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部