期刊文献+

变压器励磁涌流引起保护误动分析 被引量:44

Mal-operation analysis on magnetic inrush current of power transformer
下载PDF
导出
摘要 针对多个电厂变压器投运时的继电保护装置的误动,根据现场的故障录波波形和数据,判断出误动是由于主二保护装置没有正确进行励磁涌流闭锁造成的。具体是由于差动保护的二次谐波制动方式和二次谐波制动系数取值的不合理而造成的误动。分析了T60、RCS978谐波制动的特点;探讨了不同厂家在变压器差动保护中利用二次谐波进行制动时采取分相、或门、三取二制动的优劣和相应方式下二次谐波制动系数定值取值的合理性,并提出了减少涌流误动的措施。 Mal-operation of the relay protection equipment occurred when the transformer was put into operation in different power plants.According to the fault wave graphics and data,the mal-operation is caused by the incorrect closedown of magnetic inrush current of the second relay protection equipment.The specific reasons are the unreasonable mode and wrong coefficient value of secondary harmonic restraint.This paper analyzes the characteristics of harmonic restraint of T60 and RCS978,and discusses the advantages and disadvantages of inrush inhibit mode including per phase,or gate,2-out–of-3,together with their corresponding inrush inhibit level.Finally,it puts forward a measure to decrease the mal-operation of inrush current.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2010年第10期138-140,144,共4页 Power System Protection and Control
关键词 变压器 励磁涌流 差动 二次谐波制动 保护误动 power transformer inrush current differential protection secondary harmonic restraint mal-operation
  • 相关文献

参考文献4

二级参考文献23

  • 1孙志杰,陈云仑.波形对称原理的变压器差动保护[J].电力系统自动化,1996,20(4):42-46. 被引量:115
  • 2王祖光.间断角原理的变压器差动保护[J].电力系统自动化,1979,3(1):18-30.
  • 3陈曾田(CHENZeng-tian).电力变压器保护(Electrical Power Transformer Protection)[M].北京:中国电力出版社(Beijing:China Electric Power Press),1987..
  • 4王维俭 侯炳蕴.大型机组继电保护理论基础[M].北京:中国电力出版社,1997..
  • 5Sharp R L, Glassburn W E. A transformer differential relay with second harmonic restraint [J]. Trans. AIEE 1958,12:913-918.
  • 6Pei L, Malik O P. Deshu Chen. Improved operation of differential protection of power transformer for internal faults[J]. IEEE Trans. Power Deliv., 1992,1912-1919.
  • 7Kulidjian A, Kasztenny, Campbell B. New magnetizing inrush restraint algorithm for power transformer protection[C]. Development in power system protection, conference publication No.479 IEE2001:181-184.
  • 8Sang-Tae Kim, Bo-Geon Jin. V-I Trend-based protective relay algorithm for 3-phase power transformer [C].IEEE PES Summer Meeting,2001:605-610.
  • 9Murty Y V V S, Smolinski W J. A kalman filter based digital percentage differential and ground fault relay for 3-phase power transformer[J]. IEEE Trans. Power Deliv.1990,5(3),7:1299-1308.
  • 10Thorp J S, Phadke A G. A microprocessor based voltage restraint three phase transformer differential relay [J]. Proceeding of the south eastern symposium on system theory, 1982,4:312-316.

共引文献59