差动保护SEL387装置联结补偿设置的分析与探讨 被引量:1

Analysis and Discussion About Differential protection device SEL387 set linking the compensation
下载PDF
导出
摘要 常用的SEL387型差动保护装置的基本特点。对于SEL387联结补偿进行了分析,指出CTC(11)、CTC(0)针对于Y/Δ变压器的设置并不一定都是正确的。结合Z变接地系统发生单相接地故障的分析,得出区外故障可能误动的结论。 This paper introduces the type commonly used in differential protection SEL387 the basic characteristics of devices. SEL387 linked to a number of recognized compensation analysis, pointed out that the CTC ( 11 ), CTC (0) for the Y / △ transformer settings are not necessarily correct. Z-type transformers grounding system of single-phase ground fault analysis fault zone may maloperation con- clusions. This proposed link SEL387 It should be noted that the issue of compensation .
作者 冯爱元
出处 《天津电力技术》 2010年第2期38-43,共6页 Tianjin Electric Power Technology
关键词 差动保护 SEL387 Z变 小电流系统 零序接地 电流 联结补偿 differential protection, SEL387 ,Z-type transformers , Small current grounding system, Zero-sequence current, phase angle compensation