期刊文献+

穿管保护对ZR-VV电缆绝缘失效条件的影响 被引量:8

Effect of protecting with conduits on insulation failure of ZR-VV cable
下载PDF
导出
摘要 采用自主设计的红外辐射加热炉对不同保护状态下的ZR-VV电缆受热时的绝缘失效条件进行研究。结果表明,保护方式和加热环境对ZR-VV电缆绝缘失效温度的影响甚微,其失效温度约为183.5(1±10.7%)℃;试样的绝缘失效时间随热通量的增大显著减小,穿管保护后,时间明显延长,变化规律采用指数函数能够很好拟合;当环境的热通量较低时,穿阻燃PVC管的保护效果略优于金属管;当热通量高时,后者优于前者。 The insulation failure conditions of ZR-VV cables under different kinds of protections were studied by means of the infrared radiation reheating furnace. The test data showed that ZR-VV cable insulation failure temperature was little influenced by different protections and thermal environment, which probably remained at 183.5(1±10.7%) ℃. Thus, the cable insulation failure time was decreasing with the increase of exposure heat flux and increased when the cable was under the protection of conduit evidently, and the related variation regularity could be well fitted with exponential function model. The protective effect of fire resistant PVC conduit was much better than metal conduit when it exposed to low heat flux, but just opposite when exposed to high heat flux.
出处 《消防科学与技术》 CAS 北大核心 2010年第6期473-477,共5页 Fire Science and Technology
关键词 ZR-VV电缆 穿管保护 绝缘失效 失效温度 失效时间 ZR-VV cable protecting with conduit insulation failure failure temperature failure time
  • 相关文献

参考文献7

  • 1王炯,方纯兵.模拟实体火灾电缆特性试验技术研究[R].四川:公安部四川消防研究所,2001.
  • 2JG3050-1998,建筑用绝缘电工套管及配件[S].
  • 3GB14823.1-1993,电气安装用导管特殊要求--金属导管[S].
  • 4Keski--Rahkonen. Effect of Electrical Conductivity on Emergency Performance of Cables at High Temperatures[R]. Prague: Transactions of the 17th International Conference on Structural Mechanics in Reactor Technology (SMiRT 17), 2003.
  • 5舒中俊,贾文娜,陈南,杨守生.交联聚乙烯塑料电缆绝缘失效的实验研究[J].消防科学与技术,2009,28(11):795-799. 被引量:17
  • 6陈南.电气防火教程[M].北京:中国人民公安大学出版社,2008.
  • 7高亚萍.阻燃电缆绝缘材料聚氯乙烯热解特性研究[J].工程塑料应用,2007,35(3):44-47. 被引量:10

二级参考文献20

  • 1赵华利,王伯涛,戴殿峰.防火电线电缆的分类特性及试验方法[J].消防科学与技术,2005,24(2):220-223. 被引量:27
  • 2舒中俊,冯俊峰,陈南,方纯斌.PVC电缆及其护套原料燃烧性能的对比[J].消防科学与技术,2006,25(2):247-249. 被引量:28
  • 3潘明.火灾延续时间是消防线缆防火选型的关键因素[J].建筑电气,2006,25(4):48-53. 被引量:3
  • 4张翔,李风,刘松林.锥形量热计法研究电线电缆燃烧性能的探讨[J].消防科学与技术,2007,26(3):262-264. 被引量:11
  • 5王炯,方纯兵.模拟实体火灾电缆特性试验技术研究[R].四川:公安部四川消防研究所,2001.
  • 6IEC Standard 332- 3, Tests on electric cables under fire conditions. Part 3: Tests on bunched wires or cables[S].
  • 7IEC60331 11--1999, Tests for electric cables under fire conditions-Circuit integrity-Part 11: Apparatus-Fire alone at a flame temperature of at least 750 ℃ [S].
  • 8UL Standard 910--1998, Standard for fest for flame-propagation and smoke-density values for electrical and optical-fiber cables used in spaces transporting environmental air, Edition 5, November 23, 1998[S].
  • 9UL Standard 1581- 200t, Reference standard for electrical wires, cables, and flexible cords, Edition 4, October 31, 2001 [S].
  • 10UL Standard 1666--2000, Standard test for flame propagation height of electrical an optical-fiber cables installed vertically in shafts, Edition 4, November 28, 2000[S].

共引文献30