摘要 空气凝汽器由模块化的空冷单元组成。建立了某135 MW机组直接空冷岛空冷单元流动和传热数值模型,利用计算传热学(NHT)软件FLUENT,对不同环境风速下空冷单元进行数值模拟。经对直接空冷单元外部空气的速度场、温度场的模拟、分析和研究表明,风机风量为370.0 m3/s,空冷单元散热量为13.8 MW,即当模拟风量低于设计风量7.57%时,模拟散热量高于设计值2.76%。 The air cooled condenser(ACC) is composed of modularized air cooled elements.The flow and heat transfer model of an air cooled element used for simulation of ACC island for 135 MW unit has been established.By sing the numerical heat transfer(NHT) software named FLUENT,the numerical study on the performance of air cooled element under different environmental wind speed has been carried out.Through simulation,analysis,and investigation of the velocity field and the temperature field of air flow outside the direct air cooled element,it shows that the air flow rate is 370.0 m3/s,the radiating heat from the air cooled element is 13.80 MW,i.e.in the case of simulated air flow rate being lower than that of designed value by 5.57%,the simulated air flow rate is still higher than that of designed value by 2.76%.
出处 《热力发电》 CAS 北大核心 2010年第6期21-23,37,共4页 Thermal Power Generation
关键词 空气凝汽器 空冷单元 数值模拟 流动 传热 散热量 air cooled condenser air cooled element numerical simulation optimization design
  • 相关文献

参考文献10

二级参考文献29

  • 1张健.朔州市格瑞特实业有限公司煤矸石综合利用发电项目2×135MW发电机组直接空冷系统技术协议[R].上海:江苏双良空调设备股份有限公司,2006.
  • 2VGB technische vereinigung der grosskraftwerksbetreiber E.V..VGB guideline acceptance test measurements and operation monitoring of air - cooled condenser under vacuum VGB- R131Me[S] .Germany, 1997.
  • 3陈胜利.江苏双良空调设备股份有限公司直接空冷凝汽器系统性能试验报告[R].西安:西安热工研究院有限公司,2006.
  • 4陈胜利.钢制椭圆管矩形翅片空冷元件传热及阻力性能试验研究报告[R].西安:西安热工研究院有限公司,2006.
  • 5胡三季.钢制双列滴型管套矩形翅片空冷元件传热及阻力性能试验研究报告[R].西安:西安热工研究院有限公司,2006.
  • 6KRoGER D G. Air-cooled heat exchangers and cooling tower: thermalflow performance and design [ M ] . Oklahoma: Penwell Corporation, 1996.
  • 7MEYER C J, KRUGER D G. Air-cooled heat exchanger inlet flow losses [ J ]. Applied Thermal Engineering, 2001,21 ( 9 ) : 771 - 786.
  • 8BREDELL J R,KRoGER D G, THIART G D.Numerical investigation of fan performance in a forced draft air-ecoled steam condenser [ J]. Applied Thermal Engineering,2006,26(8) : 846 - 852.
  • 9HOTCHKISS P J, MEYER C J, VON BACKSTOM T W. Numerical investigation into the effect of cross-flow on the performance of axial flow fans in forced draught air-cooled heat exchangers [J]. Applied Thermal Engineering, 2006,26(2) : 200 - 208.
  • 10EYER C J. Numerical investigation of the effect of inlet flow distortions on forced draught air-cooled heat exchanger performance [J]. Applied Thermal Engineering, 2005,25 ( 11 ) : 1634 - 1649.