摘要
用快速阻垢测试方法和热水系统模拟试验法,研究证实了电子水处理器具有显著的阻垢效果,其阻垢率与电压、水质、温度等因素有关。在循环冷却水系统中阻垢率可达960%以上。在热水系统中阻垢率大于947%。根据试验现象和水质变化。
Abstract The significant scaling inhibition of electronic water arrester was confirmed by a simulating research in hot water system with fast scale inhibition test. The scale inhibition is correlated to the voltage, the composition of water and the temperature etc and it exceeded 96% in the circulating cooling water system and 94 7% in the hot water system respectively. The mechanism of the electronic water arrester is discussed on the basis of the phenomenon observed and the changes of water quality in the experiment.
出处
《给水排水》
CSCD
北大核心
1999年第1期40-43,共4页
Water & Wastewater Engineering