期刊文献+

新型置换通风系统耦合作用机理分析研究 被引量:9

Study on the Coupling Mechanism of the New Displacement Ventilation System
下载PDF
导出
摘要 建立了办公室房间侧墙上置风口置换通风方式试验模型,测试了不同负荷情况下房间非等温送风射流的速度分布和温度分布。利用无因次速度变化曲线,分析了送风射流的发展规律,依据送风射流边界层理论,分析了房间内送风射流与周围空气热质交换以及送风射流与热羽流对房间温度分层的影响,阐明了新型置换通风系统耦合作用机理。 The experimental model of the displacement ventilation system with high sidewall outlet used for a office room was built,the velocity distribution of the non-isothermal air supply jet and the temperature profile in the room under different load conditions was tested.Using dimensionless velocity change curve of the ventilation jet,the air supply jet flow regulation was analyzed,and the heat and mass transfer between air supply jet and ambient air in the room based on the boundary layer theory of air supply jet was analyzed.The influence of air supply jet and thermal plume on the thermal stratification was explained,the coupling mechanism of the new displacement ventilation system was presented.
作者 王智伟 郭聪
出处 《流体机械》 CSCD 北大核心 2010年第6期1-5,10,共6页 Fluid Machinery
基金 陕西省教育厅专项科研计划项目(07JK297) 西安建筑科技大学基础研究基金项目(JC0710)
关键词 上置风口 置换通风 非等温送风射流 热质交换 耦合作用机理 up-fixing diffusers displacement ventilation non-isothermal air supply jet heat and mass transfer coupling mechanism
  • 相关文献

参考文献8

二级参考文献22

  • 1王晓彤,陈俊俊,李义科,武文斐.热源特性对置换通风热力分层高度影响的分析[J].建筑热能通风空调,2005,24(3):69-72. 被引量:5
  • 2马仁民 王怡.水平置换通风防止风感及致适条件[A]..全国暖通空调制冷1998年学术文集[C].,1998..
  • 3马仁民.论空气分布对送风系统通风效果的影响[A]..全国暖通空调制冷1996年学术年会论文集[C].,1996..
  • 4Elisabeth Mundt. The performance of displacement ventilation system[ D ]. Sweden:Royal Institute of Technology, 1996.
  • 5张旺达.竖壁贴附射流及其空气池现象的预测与可视化验证[D].西安:西安建筑科技大学,2006.
  • 6Abdel-fattah A. Numerical and experimental study of turbulent impinging twin - jet flow [ J ]. Experimental Thermal and Fluid Science,2007,31:1 061 - 1 072.
  • 7Alain Triboix, Daniel Marchal. Stability analysis of the mechanism of jet attachment to walls [ J ]. International Journal of Heat and Mass Transfer,2002,45:2 769 -2 775.
  • 8[1]Svensson,A.G.L.Nordic Experience of Displacement Ventilation Systems[J].ASHRAE Transactions,1989,95(2):1013-1017.
  • 9[4]YUAN Xiao-xiong.CHEN Qing-yan.System Performance Evaluation and Design Guidelines for Displacement Ventilation[J].ASHRAE Transaction,2003.
  • 10[5]A.K.Melikov,J.B.Nielsen.Local Thermal Discomfort Due to Draft and Ventical Temperature Difference in Rooms with Displacement Ventilation[J].ASHRAE Transaction,1989,95(2):1050-1057.