摘要
文章通过对三峡投标机组绕组结构的详细分析,针对可能的内部故障,采用故障分量法计算出相应的差动电流,并以Ⅰ、Ⅲ号机组为例,分析了两台机组发生内部故障时各种保护方案的灵敏度,并详细讨论了内部故障的保护配置。
After analyzing the winding structure of generators in Three Gorges Hydropowerstation, an algorithm for inner faults which will occur possibly is described in this paper. With fault components the relevant differential current can be calculated by this algorithm. The sensibility of all kind of protection scheme is given and the main protection scheme for internal faults is presented.
出处
《电网技术》
EI
CSCD
北大核心
1999年第1期4-8,共5页
Power System Technology
关键词
大型发电机组
故障分析
差动保护
发电机组
Phase to phase short circuit Turn to turn short circuit Turn ratio Differential protection