不同老化因素对油纸绝缘介质频域谱特性的影响 被引量:64

Infuence of Different Aging Conditions on Characteristics of Frequency Domain Spectroscopy of Oil-paper Insulation Medium
下载PDF
导出
摘要 为获取表征油纸绝缘老化状态的新特征量,实现将频域谱技术用于变压器老化状态的无损诊断,在实验室条件下系统地研究了不同热老化程度、不同测量温度以及不同含水量下油纸绝缘试品的频域谱(FDS)变化规律,并运用电介质极化理论对其影响机理进行了分析。结果表明,绝缘纸的相对介电常数虚部和介质损耗角正切值tanδ在频率<100Hz时随其老化的深入而显著增加;水分作为一种强极性分子,使得油纸绝缘试品的FDS曲线随含水量增加而明显上移;同时,研究发现将FDS用于油纸绝缘状态诊断时必须充分考虑测试温度的影响。 In oder to obtain the new characteristics of oil-paper insulation aging and realize non-destructive diagnosis of the transformer ageing state by frequency domain spectrum technology,we investigated the changing regularity of frequency domain spectroscopy under laboratory conditions,including different degree of thermal aging,different measurement temperatures,and different moisture content of oil-paper insulation test products. And using the theory of dielectric polarization,we analyzed the reflected mechanism. The results show that,the imaginary part of relative dielectric constant of insulating paper and dielectric loss angle tangent tanδ increase significantly at a frequency of 100 Hz with the aging of the following. The strong polar molecule moisture content significantly increases the FDS curve of oil-paper insulation test with increasing moisture content. Moreover,it is found that the impact of the test temperature must be fully considered when using the FDS for diagnosis the oil-paper insulation.
出处 《高电压技术》 EI CAS CSCD 北大核心 2010年第7期1612-1618,共7页 High Voltage Engineering
基金 国家重点基础研究发展计划(973计划)(2009CB724505-1)~~
关键词 介质响应 频域谱(FDS) 油纸绝缘 热老化 含水量 温度 dielectric response frequency domain spectroscopy(FDS) oil-paper insulation thermal aging moisture content temperature
  • 相关文献

参考文献21

  • 1Pahlavanpour B, Linaker R, Povazan E. Extension of life span of power transformer on-site improvement of insulating materials[C]// IEE Colloquium on Assessment of Degradation Within Transformer Insulation Systems. London, UK: IEE, 1991: 6/1 -6/4.
  • 2速水敏幸.电力设备的绝缘诊断[M].北京:科学出版社,2003..
  • 3廖瑞金,解兵,杨丽君,梁帅伟,程涣超,孙才新,向彬.油纸绝缘电-热联合老化寿命模型的比较与分析[J].电工技术学报,2006,21(2):17-21. 被引量:36
  • 4Ali M, Eley C, Emsley A M, et al. Measuring and understanding the ageing of kraft insulating paper in power transformers [J]. IEEE Electrical Insulation Magazine, 1996, 12(3): 28-33.
  • 5吴斌.如何评价国产500kV变压器[J].变压器,1996,33(12):2-8. 被引量:3
  • 6贺以燕.关于电力变压器承受短路能力问题的再探讨[J].变压器,1996,33(11):2-4. 被引量:33
  • 7Shang Y, Yang L, Guo Z J, et al. Assessing aging of large transformers by furfural investigation[C] // 2001 IEEE 7th International Conference on Solid Dielectrics. Eindhoven, the Netherlands: IEEE, 2001:272- 274.
  • 8廖瑞金,冯运,杨丽君,向彬,刘刚.油纸绝缘老化特征产物生成速率研究[J].中国电机工程学报,2008,28(10):142-147. 被引量:87
  • 9Kan H, Miyamoto T, Makino Y, et al. Absorption of CO2 and CO gases and furfural in insulating oil into paper insulation in oil-immersed transformers[C]//Conference Record of IEEE International Symposium on Electrical Insulation. Pittsburgh, PA, USA: IEEE, 1994: 41.
  • 10Pahlavanpour P, Eklund, Martins M A. Insulating paper ageing and furfural formation[C]//2003 Electrical Insulation Conference and Electrical Manu/acturing & Coll Winding Technology Conference Proceedings. Toronto, Canada : [ s. n. ], 2003 : 283-288.

二级参考文献31

共引文献181

同被引文献581

引证文献64

二级引证文献596

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部