期刊文献+

白雾防止型密闭式喷淋冷却塔试验研究 被引量:4

Experimental study on a closed wet anti-white mist spray cooling tower
下载PDF
导出
摘要 为了防止冷却塔产生白雾,设计并制造了一种密闭式喷淋冷却塔。在该冷却塔中,冷却水分成两路分别在湿式换热器和干式换热器中冷却降温。湿式换热器采用铜翅片管,冷却水通过铜管向喷淋水释放热量,而喷淋水则和来流空气在翅片管表面进行传热传质。低温高湿的空气流过干式换热器后被铜铝复合翅片管内的冷却水加热,因此空气出口温度升高,使得出口空气和外部空气混合后的状态点不与饱和空气线相交,从而避免了白雾的产生。 In order to avoid the formation of white mist in the outlet airflow coming from cooling towers,a closed wet spray cooling tower was designed and manufactured.In the said cooling tower,cooling water is separa-ted and cooled in wet heat exchanger and dry heat exchanger respectively.In the wet heat exchanger,which adopts copper fin tubes as heat transfer tubes,cooling water is chilled inside the heat transfer tubes while heat and mass transfer between spray water and airflow is observed outside the copper tubes.The airflow with low tem-perature and high humidity flows across the dry heat transfer,and then,heated by the cooling water in copper-aluminum combined fin tubes,which causes a high outlet temperature of the airflow.As a result,when the outlet airflow mixes with ambient air,the mixed airflow is unsaturated,which avoid the formation of white mist.
出处 《工业用水与废水》 CAS 2010年第4期72-74,79,共4页 Industrial Water & Wastewater
关键词 冷却塔 白雾 饱和 换热器 cooling tower white mist saturation heat exchanger
  • 相关文献

参考文献5

  • 1Policastro A J,Dunn W E,Carhart R A.A model for seasonal and annual cooling tower impacts[J].Atmospheric Environment,1994,28(3):379-395.
  • 2Koenig L R.Anomalous snowfall caused by natural-draft cooling towers[J].Atmospheric Environment,1981,15(7):1117-1128.
  • 3Kramer M L,D E Seymour,M J Butler,et al.Cooling tower flight program data December 1974-March 1975,by Smith/Singer Meteorolngists[R].New York:Ine Amityville,N.Y.for American Electric Power Service Coep.OH,1975.
  • 4Orville H D,Hirsch J H,May L E.Application of a cloud model to cooling tower plumes and clouds[J].Journal Applied Meteor,1980,19(11):1260-1272.
  • 5唐韵.低下冷却器的紧凑性及防白雾研究[D].上海:上海交通大学,2007.

同被引文献22

  • 1周兰欣,蒋波,陈素敏.自然通风湿式冷却塔热力特性数值模拟[J].水利学报,2009,39(2):208-213. 被引量:41
  • 2杨昭,郁文红,吴志光.火力发电厂冷却塔除雾收水的热力学分析[J].天津大学学报(自然科学与工程技术版),2004,37(9):774-777. 被引量:14
  • 3卢洪发.日本防止冷却塔发生羽烟的技术措施[J].东方电气评论,1994,8(2):117-122. 被引量:6
  • 4陈则韶,江斌,史敏,樊高定.影响热泵COP的因素与节能途径分析[J].流体机械,2007,35(1):64-68. 被引量:16
  • 5张涣武.干-湿式冷却塔[A].冷却塔研究会成立暨技术交流大会论文集[C].合肥:全国化工给排水设计技术中心站,2004.
  • 6Koening L R, Anomalous snowfall caused by natural-draft cooling towers[J]. Atmospheric Environment, 1981, 15(7): 1117-1128.
  • 7Kramer M L, Seymour D E, Butler M J, et al. Cooling tower flight program data December 1974-March 1975, by Smith/Singer Meteorologists[R]. NewYork: Inc Amityville, N.Y. for American Electric Power Service Coep. OH., 1975.
  • 8Orville H D, Hirsch J H ,May L E. Application of a cloud model to cooling tower plumes and clouds[J]. Journal Applied Meteor, 1980,19(11): 1260-1272.
  • 9Policastro A J, Dunn W E, Carhart R A. A model for seasonal and annual cooling tower impacts[J]. Atmospheric Environment, 1994, 28(3): 379-395.
  • 10谭小卫.一种基于出风温湿度检测的冷却塔防白雾控制装置[P].中国:ZL201220317582.2013-02-20.