摘要
在机组启停及低负荷运行期间,锅炉辅助蒸汽汽源能否正常供应对机组的正常启停和安全运行将带来一定的影响。本文就华能福州电厂一期工程两台日本三菱亚临界强制循环锅炉辅助蒸汽运行的安全性进行分析,并分析了机组启停及低负荷运行期间辅助蒸汽汽源由过热与再热汽源互为切换过程中出现压力大幅度降低的原因,对日方原设计不合理的控制系统进行了改造。
Abstract Proper operation
of auxiliary steam supply system is very important to boiler unit during start-up,shutdown and
low-load operation.This paper presents an analysis to the operation safety of the auxiliary steam
supply system of two subcritical forced circulation boilers in Huaneng Fuzhou Power Plant.It also
gives some detail analysis to the causes of large descent of auxiliary steam pressure during the
switchover between the superheated steam and the reheated steam.
出处
《热力发电》
CAS
北大核心
1999年第3期35-36,共2页
Thermal Power Generation