浅析框架-核心筒结构设计中的几个问题 被引量:3

Analysis of Some Issues for Design of Frame-Shearing Wall Structures
下载PDF
导出
摘要 某新建办公楼总高90 m,采用框架-核心筒结构。考虑到安全储备,严格按照考虑双向地震(X向,Y向)框架部分承受的地震倾覆力矩均小于50%进行设计;地下室顶板在满足嵌固的构造及刚度比要求的条件下,模型建立时计入地下室作整体分析,所得周期及位移比参数相比把地下室当作大底板更接近于实际情况;最后通过底部剪力墙截面面积与楼面面积之比判断剪力墙数量的合理性。 Some issues on design of frame-shear wall structures based on an actual building project case are discussed. For the safety purpose,the seismic overturning moments in X and Y direction heated by frames are less than 50% for the studied case. Under the condition of the fixed condition of basement floor slab and the condition that the stiffness ratio are satisfied, the calculated periods and displacement ratios will be more accurate than the model without the basement structures when the basement structures can be added into the whole building calculation model. Finally the rationality of the structural design can be assessed by checking the ratio of shear-wall cross-sectional area to the floor area.
作者 洪婷婷
出处 《结构工程师》 2010年第4期15-20,共6页 Structural Engineers
关键词 框架-核心筒 倾覆力矩 剪力墙截面面积 合理性 frame-shearing wall structure, seismic overturning moment, shear-wall cross-sectional area, rationality
  • 相关文献

参考文献6

二级参考文献21

  • 1徐培福,戴国莹.超限高层建筑结构基于性能抗震设计的研究[J].土木工程学报,2005,38(1):1-10. 被引量:224
  • 2方德平,王全凤.变刚度框剪结构地震反应的层单元分析[J].建筑结构,2005,35(11):36-38. 被引量:5
  • 3冯宏团,张海龙.框-剪结构剪力墙中断分析[J].建筑结构,2005,35(12):45-46. 被引量:2
  • 4[8]中华人民共和国建设部.GB 50011-2001建筑抗震设计规范[S].北京:中国建筑工业出版社,2001.
  • 5[4]上海市建委科学技术委员会.上海市超限高层建筑工程抗震设防专项审查选编[M].2006,2007.
  • 6.建筑桩基技术规范(JGJ 94-94)[M].北京:中国建筑工业出版社,1995..
  • 7.工程结构设计基本术语和通用符号(GBJ 132-90)[M].北京:中国计划出版社,1991..
  • 8.全国民用建筑工程设计技术措施-结构[M].北京:中国计划出版社,2003..
  • 9DGJ08-11-1999.地基基础设计规范上海市工程建设规范.[S].,..
  • 10.建筑结构可靠度设计统一标准(GB 50068-2001)[M].北京:中国建筑工业出版社,2001..

共引文献24

同被引文献19

引证文献3

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部