期刊文献+

结霜工况风量对风冷热泵性能影响的研究 被引量:1

Experimental study of the facing airflow on the performance of air-to-water heat pump unit under frosting conditions
下载PDF
导出
摘要 针对一台名义制冷量为50kW的风冷热泵冷热水机组,实验研究了迎面空气流量变化对机组结霜工况性能的影响。实验结果表明,结霜条件下,迎面空气流量降低促使机组工作性能大幅降低;迎面空气流量的变化对V型换热器表面霜层分布没有影响。空气流量的降低只是造成换热器表面结霜量的增多,适当提高风机转速具有抑制结霜、有效提高机组运行性能的作用;来流风速的不均匀分布对结霜以及霜层的分布有重要影响。 The experiments were conducted on a 50kW unitary air-to-water heat pump unit and discussed for different airflow under frosting conditions.The results indicate that the working performance of unit is decreased dramatically with the airflow decreasing under frosting conditions.It was also found that the airflow flux has little effect on the frost distribution and the frost accumulation increases with the decrease of the airflow.It was inferred that the unit works well with increasing fan speed in some extent.It is necessary to study the effect of airflow maldistribution on the frosting process for V type heat exchanger.
出处 《低温与超导》 CAS CSCD 北大核心 2010年第9期65-68,共4页 Cryogenics and Superconductivity
关键词 风冷热泵冷热水机组 结霜 工作性能 Air-to-water heat pump unit Frosting Working performance
  • 相关文献

参考文献7

二级参考文献36

  • 1郭宪民,游立新,沈增友.结霜工况下直接蒸发式空气冷却器的计算机辅助设计[J].流体工程,1993,21(1):49-54. 被引量:6
  • 2姬长发,黄东,袁秀玲.风冷热泵冷热水机组结霜与除霜性能的实验研究[J].西安交通大学学报,2005,39(5):480-484. 被引量:13
  • 3刘维华,白梓运,陈芝久.膨胀阀动态响应特性的实验研究[J].流体机械,1995,23(7):60-62. 被引量:1
  • 4Ogawa K,Tanaka N,Takeshita M.Performance improvement of plate fin-and tube heat exchanger under frosting condition[J].ASHRAE Transactions,1993,99(1):762-771.
  • 5O'Neal D L,Tree D R.A review of frost formation in simple geometries[J].ASHRAE Transactions,1985,91(1):267-281.
  • 6Padki M M,Sherif S A,Nelson R M.A simple method for modeling the frost formation phenomenon in different geometries[J].ASHRAE Transactions,1989,95(2):1127-1137.
  • 7Chen H,Thomas L,Besant R W.Modeling frost characteristics on heat exchanger fins:numerical modeling[J].ASHRAE Transactions,2000,106(2):358-367.
  • 8Chen H,Thomas L,Besant R W.Measurement of frost characteristics on heat exchanger fins:data and analysis[J].ASHRAE Transactions,1999,105(2):294-302.
  • 9Ogawa K,Tanaka N,Takeshita M.Performance improvement of plat fin-and-tube heat exchangers under frosting conditions [J].ASHRAE Trans,1993,99(1):762-771.
  • 10Yao Y,Jiang Y Q,Deng S M,A study on the performance of the airside heat exchanger under frosting in a air source heat pump water heater/chiller unit [J].Int J of Heat and Mass Transfer,2004,47(17-18):3745-3756.

共引文献84

同被引文献11

引证文献1

二级引证文献11

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部