低气压下绝缘子串直流污闪放电模型及验证 被引量:10

DC Pollution Flashover Model and Its Validation of Polluted Insulator Strings Under Low Air Pressure
下载PDF
导出
摘要 为揭示低气压下染污绝缘子串闪络机理,并为低气压地区外绝缘选择和设计提供参考,在人工气候室模拟低气压条件,以7片串XP-160绝缘子为例,进行了不同低气压、污秽下绝缘子直流放电特性试验研究,并拍摄了其放电过程。试验结果表明:低气压下直流污闪放电过程中局部电弧存在飘弧现象,因此提出低气压下染污绝缘子串直流放电过程的电路模型是由剩余污层电阻、沿面电弧和空气间隙电弧串联组成;根据模型计算所得的临界污闪电压与实测值的误差在10%以内;揭示了静电力和热浮力随气压变化规律的差异是低气压下局部电弧发展中飘弧现象更严重的主要原因。 To reveal the flashover mechanism of polluted insulator strings and to offer some consult for the external insulation selection and design under low air pressure,a series of tests were carried out in the low air pressure condition simulated by artificial climate chamber.Taking 7 units of XP-160 for examples,we experimentally researched the DC discharge performance of insulator at different low air pressure and pollution degree in which the discharge process was taken by high speed vidicon.The experimental results show that some of the partial arcs may deviate from the surface of insulator string and form the air gap arc during the DC pollution flashover discharge process under low air pressure.So a circuit model explaining the DC discharge process of polluted insulator strings under low air pressure is given,which consists of a surface arc,air gap arc and residual resistance of the pollution layer.The relative error of critical pollution flashover voltage got by the model and the experimental results is lower than 10%.The results reveal that the difference between influences of air pressure on electrostatic force and thermal buoyant force is the main reason which makes the partial arc deviated from the surface of insulator more severely under low air pressure.
出处 《高电压技术》 EI CAS CSCD 北大核心 2010年第9期2126-2131,共6页 High Voltage Engineering
基金 国家重点基础研究发展计划(973计划)(2009CB724503) 重庆大学青年骨干教师创新能力培育基金(2008CX001)~~
关键词 低气压 污秽 直流 绝缘子串 闪络过程 局部电弧 电路模型 low air pressure pollution DC insulator string flashover process partial arc circuit model
  • 相关文献

参考文献16

  • 1Bergman V I,Kolobova O I. Some results of investigation of the dielectric strength studies of contaminated line insulation under lower air pressure conditions[J]. Elektrotekhnika, 1983,54(2): 14-18.
  • 2Kawamura T. Pressure dependence of de breakdown of contaminated insulators[J]. IEEE Transactions on Electrical Insulation, 1982,17(1) :39-45.
  • 3Ishii M, Shimada K. Flashover of contaminated surface under low atmospheric pressure[C]// Proceeding of the 4th International Symposium on High-Voltage Engineering. Athens, Greece: [s. n.], 1983:46-51.
  • 4Zhang R, Zheng J. Progress in outdoor insulation research in China[J]. IEEE Transactions on Eleetrieal Insulation, 1990,25 (6) : 1125-1137.
  • 5张仁豫,关志成,黄超峰.低气压对玻璃板表面污闪电压的影响[J].电网技术,1994,18(3):17-21. 被引量:15
  • 6Farzaneh M, Zhang J, Li Y. Effects of low air pressure on AC and DC arc propagation on ice surface[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2005,12(1) : 60-71.
  • 7张志劲,蒋兴良,胡建林,孙才新.低气压下的直流电弧特性[J].高电压技术,2009,35(4):790-795. 被引量:14
  • 8Rizk F A M. Modeling of altitude effects on AC flashover of polluted high voltage insulators[J]. IEEE Transactions on Power Delivery, 1997,12(2) :810-822.
  • 9IEC 1245 Artificial pollution tests on high-voltage insulators to be used on DC system[S],1993.
  • 10CIGRE WG' S-33.04. Artificial pollution testing of HVDC insulators: analysis of factors influencing performance [J]. Electra,1992(140) :99-113.

二级参考文献95

共引文献89

同被引文献150

引证文献10

二级引证文献57

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部