摘要
分析了现有行波故障测距方法所存在的问题,在单端行波测距法的基础上推导出一种与行波波速无关的测距方法,然后将此方法与传统双端行波测距方法相结合形成一种组合测距方法。这种方法在测量端的近端线路故障时采用传统双端测距方法,解决了近端测距的盲区问题;在非近端故障时采用波速无关的测距方法,提高了测距精度。
The existing problems of the current fault location methods based on travelling wave are analyzed,and a location method is derived which is unrelated to wave velocity.Then a combined location method is formed which combines the above-mentioned location method with the traditional two-terminal location method.The traditional two-terminal location method is used to solve the blind zone problem of near-end fault location,and the location method which is unrelated to wave velocity is used to improve the location precision of the far-end fault.
出处
《四川电力技术》
2010年第5期19-22,52,共5页
Sichuan Electric Power Technology
关键词
电力电缆
行波
故障测距
组合方法
power cable
travelling wave
fault location
combined method