摘要
由于两功率表法不能测量三相四线制电路中的零序功率,采用此法将少计量功率,这早已为许多从事电量测试和计量的人员所认识。但在实际测量中,有可能比实际功率多计量,也可能比实际功率少计量。文中以火铺火电厂的110 kV升压变压器为例,通过现场实测数据,并对测量的数据进行分析,判断正负测量误差。通过分析该测量方式带来的测量误差来规范测量回路,减小关口电能表的测量误差,对电力企业、电力设计单位、施工单位都有着极为重要的意义。
As the active power of zero-sequence circuit can not be measured in the three-phase four-wire circuits by two power meters,this method will lead to less power energy in measurement,In practical measurement,it may have more power than the actual measurement,may also be less than the actual power measurement.In this paper,by taking the step-up transformer of 110 kV in HuoPu power plant for example and using recorded field data,positive and negative measurement errors are judged by analyzing these data.The measurement error is analyzed to standardize measurement circuits and reduce the errors of gate energy meters in measurement,which have a very important significance to power enterprises,power design organizations and construction organizations.
出处
《电力系统及其自动化学报》
CSCD
北大核心
2010年第5期76-79,共4页
Proceedings of the CSU-EPSA
基金
云南省教育科学规划课题GG09017
昆明理工大学教育技术研究项目08X01
关键词
三相四线制
两功率表法
零序有功功率
正负测量误差
电能计量
three-phase four-wire circuit
two power meter method
zero sequence active power
positive and negative measurement errors
measurement of power energy