期刊文献+

±800kV/4750A特高压直流换流阀宽频建模及电压分布特性研究 被引量:23

Study on Wide-band Model and Voltage Distribution of 800 kV/4750 A UHVDC Valves
下载PDF
导出
摘要 直流输电换流阀的电压分布性能是其重要电气特性之一。它不但影响换流阀的可靠性,甚至也影响阀的成本。而电压性能的计算不但与分析方法有关,也受电路模型精确度的影响。针对±800kV/4750A特高压换流阀建立宽频电路模型,试验和仿真结果表明所建的宽频模型是可行的,并具有较高的精确度。此外,也就电路元件参数和杂散电容对该特高压换流阀电压分布的影响进行分析,并总结其中的关键因素。结果表明对于阀的电压分布性能来说,饱和电抗器设计和阀层对地杂散电容尤为重要。 The voltage distribution performance of high voltage DC (HVDC) converter valve is one of important research contents about its electric characteristics. It influences the reliability even cost of converter valve. However, the calculation of voltage distribution performance is affected by analysis method and the circuit model of converter valve. In this paper, the wide-band model of +800 kV/4 750 A ultra HVDC (UHVDC) converter valve was built. The results of test and simulation indicate that the model is available. Further, both the influences of power circuit parameters and stray capacitances on the voltage distribution of such a converter valve were investigated and the key factors were also summarized. They indicate that for even voltage distribution, both the design of saturable reactor and the value of stray capacitances between valve layers and earth are important.
出处 《中国电机工程学报》 EI CSCD 北大核心 2010年第31期1-6,共6页 Proceedings of the CSEE
基金 国家电网公司科技项目(SGKJ[2007]107) 国家科技部科技项目(2006BAA02A27)~~
关键词 特高压直流输电 换流阀 电压分布 宽频模型 ultra high voltage DC (UHVDC) convertervalve voltage distribution wide-band model
  • 相关文献

参考文献2

二级参考文献39

  • 1贺之渊,邓占锋,查鲲鹏,汤广福.晶闸管阀过电流试验装置过电压保护策略的研究[J].中国电机工程学报,2006,26(13):56-61. 被引量:18
  • 2鲁宗相,刘文华,王仲鸿.基于k/n(G)模型的STATCOM装置可靠性分析[J].中国电机工程学报,2007,27(13):12-17. 被引量:18
  • 3Liu Y, Sebo S A, Wright S E. Modeling of converter transformer using frequency domain terminal impedance measurements[J]. IEEE Trans. on Power Delivery, 1993, 8(1): 66-72.
  • 4Ross C, Robert V D, Kasten D G, et al. HVDC converter station tests in the 0.1 to 5MHz frequency range[J]. IEEE Trans. on Power Delivery, 1988, 3(3): 971-977.
  • 5Maruvada P S, Malewski R, Wong P S. Measurement of the electromagnetic enviroment of HVDC converter stations[J]. IEEE Trans. on Power Delivery, 1989, 4(2): 1129-1136.
  • 6Dallaire R D, Maruvada P S. Evaluation of the effectiveness of shielding and filtering of HVDC converter stations[J]. IEEE Trans. on Power Delivery, 1989, 4(2): 1469-1475.
  • 7Jakel B W, Quoc-Bu T. Electromagnetic environment near HVDC thyristor valves[C]. Eleventh International Symposium on High Voltage Engineering, London, UK, 1999.
  • 8Murata Y, Tanabe S, Ukawa Y, et al. 3D-MoM analysis of radio frequency noise radiation from HVDC converter station[C]. IEEE International Symposium on Electromagnetic Compatibility, Seattle, USA, 1999.
  • 9Gustavsen B, Semlyen A. Rational approximation of frequency domain responses by vector fitting[J]. IEEE Trans. on Power Delivery, 1999, 14(3): 1052-1061.
  • 10Brune O. Synthesis of a finite two-terminal network whose driving-point impedance is a prescribed function of frequency[J]. Journal of Mathematical Physics, 1931, 10(2): 191-236

共引文献50

同被引文献210

引证文献23

二级引证文献188

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部