期刊文献+

10kV直配线路单相断线兼接地故障实用诊断方法 被引量:4

A Practical Method for Line-open with Line-to-ground Fault Diagnosis on 10kV Direct Distribution Lines
下载PDF
导出
摘要 本文提出了一种利用线路单端信息实现单相断线兼接地故障测距的新算法。本文法采用分布参数电路模型,利用对称分量法,于故障后在线路始端施加正弦诊断信号,并检测起始端口的电压电流相量,以此实现故障点的精确测距,大量的计算机仿真和在模型线路上的试验表明,本方法具有很高的精度。 This paper presents a new technique for accurately locating faults on 10kV direct distribution lines The technique utilizes singles at initial end of the line By the way of a distributed parameter circuit model constructed,symmetrical components method used,sine detection single given and voltage phasors detected at initial end,the fault location is completed accurately A lot of fault diagnosis simulation by computer and on fault model lines shows the method in the paper is effective \ \
出处 《广西工学院学报》 CAS 1999年第1期45-49,共5页 Journal of Guangxi University of Technology
关键词 故障定位 配电线路 故障诊断 单相断线 接地故障 Fault location Distribution network Distributed parameter model Fault diagnosis
  • 相关文献

参考文献1

二级参考文献20

  • 1徐丙垠,朱锡贵,马长贵.行波特征鉴别式距离保护原理的研究[J].中国电机工程学报,1989,9(3):1-8. 被引量:26
  • 2陈腊生,孙淑信.探测平行双回线路故障距离的一种计算方法[J].电力系统自动化,1990,14(1):26-33. 被引量:2
  • 3周玉江,黄焕焜.探测故障距离的新方法[J]电力系统自动化,1988(05).
  • 4冯载生.利用零序电流比值分布曲线确定接地故障点的方法[J]电力系统自动化,1988(04).
  • 5陆继璜.同杆双回线微机距离保护的设计和试验[J]电力系统自动化,1988(02).
  • 6杨志刚.用故障录波图进行精确故障定位的研究[J]继电器,1987(02).
  • 7王广学.电力系统接地故障点的分析计算方法[J]电力系统自动化,1986(04).
  • 8吴国瑜.用贝瑞隆法作行波继电保护的计算及其程序设计[J]电力系统自动化,1985(03).
  • 9叶一麟,蔡德礼.系统参数变化对输电线路故障测距精度的影响[J]重庆大学学报(自然科学版),1984(04).
  • 10杨奇逊.计算机继电保护的发展和应用的若干问题[J]电力系统自动化,1983(03).