期刊文献+

牵引供电新型异相短路保护原理的研究 被引量:11

Research on new protection principle against wrong-phase short circuit of the AC traction supply
下载PDF
导出
摘要 在建立电弧模型的基础上,对异相电弧短路故障信号进行仿真分析,证明原有的馈线保护原理存在缺陷。对牵引供电系统异相电弧短路故障发生时,各相电压电流的谐波特点进行分析研究,提出了通过检测异相短路两供电臂间电压来确认异相短路发生时的低压保护方案。通过对轻、重载和单臂、双臂工况下发生异相电弧短路故障时的两供电臂间相间电压仿真,验证了该保护方案的正确性,有效性和可行性。这种保护方案可作为牵引网异相短路的主保护,并与牵引网馈线成套保护结合,组成牵引网完整的保护策略。 The fault sign of wrong-phase arc short circuit is simulated and analyzed by building arc model. The flaw of the existing feeder protection principle is proved. Based on the analysis of the harmonics characteristics of each phase voltage and current that result from wrong phase arc short circuit, the low voltage protection principle by detecting the voltage between the two supply arms is proposed to confirm the appearance of wrong phase short circuit. The correctness, effectiveness and feasibility of the protection principle are verified by simulations of the voltage between the two supply arms in the conditions of the light load, heavy load, and one arm, two arms short circuit. This protection principle can be used as the main protection against wrong phase arc short circuit in traction network, and it can be combined with traction supply feeder complete protection to form a complete protection strategy.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2010年第22期63-67,共5页 Power System Protection and Control
基金 中央高校基本科研业务费专项资金科技创新项目(SWJTU09CX030)
关键词 牵引供电系统 异相电弧短路 电弧模型 谐波分析 AC traction supply system wrong-phase arc short circuit arc model harmonic analysis
  • 相关文献

参考文献4

二级参考文献5

  • 1陈维荣,学位论文,1998年
  • 2简克良,高电压技术,1993年,19卷
  • 3贺威俊,铁道学报,1986年,8卷,1期,36页
  • 4刘万顺,电力系统故障分析,1986年
  • 5O. Mayr. Beitr?ge zur Theorie des statischen und des dynamischen Lichtbogens[J] 1943,Archiv für Elektrotechnik(12):588~608

共引文献66

同被引文献70

引证文献11

二级引证文献119

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部