期刊文献+

数字化变电站光纤差动保护同步新方法 被引量:17

A New Synchronization Method of Optical Fiber Line Differential Protection for Digital Substation
下载PDF
导出
摘要 在使用电子式互感器的数字化变电站中,实现差动保护的关键是两侧电气量的同步。提出了解决该问题的新方法:首先,通过统一时钟源完成数字化变电站侧的保护装置和间隔合并单元的同步;然后,通过插值法得到保护用交流量数据;最后,通过采样时刻调整法完成站间保护装置的同步,从而实现两侧电气量的同步。 In digital substations with electronic transformers, the key for implementation of line differential protection is the synchronization of electrical quantities at both two sides. A new method is proposed to solve the problem. First, merging unit (MU) and protection device of digital stations are synchronized by unified clock source. Then data of ac quantities used for protection are calculated with interpolation method. Finally, protection devices synchronization in substations at two sides are completed by sampling time adjustment method. And the synchronization of electrical quantities at both sides is achieved.
出处 《电力系统自动化》 EI CSCD 北大核心 2010年第22期90-92,共3页 Automation of Electric Power Systems
关键词 电子式互感器 数字化变电站 光纤差动保护 同步 插值法 采样时刻调整法 electronic transformer digital substation optical fiber differential protection synchronization interpolation method sampling time adjusting method