期刊文献+

人员密度设定对地下商业空间空调设计的影响

Influence of occupant density on HVAC system design in underground commercial spaces
下载PDF
导出
摘要 人员密度设定对地下商业空间空调负荷计算、空调系统设计有着重要的影响,以济南某地下商业空间为例,定量描述了上述影响,提出了人员密度的取值思路及相关参考数据,给出了在不同人员密度下一次回风定风量系统冬、夏季的处理极限,对比了冬、夏季风量,结果显示,等送风温差下,冬季风量较夏季风量大。 Quantitatively describes the influence based on a real project in Jinan,Shandong Province.Studies the way to determine the occupant density value and supplies the related data.Calculates indoor conditions which can be handled by primary return air system with constant air volume under different occupant density and compares the air mass flow in summer and winter respectively.The analysis result shows that when supplying air under the constant temperature difference,the air mass flow will be larger in winter conditions.
出处 《暖通空调》 北大核心 2010年第12期33-37,共5页 Heating Ventilating & Air Conditioning
关键词 地下商业 人员密度 空调负荷计算 一次回风系统 underground commercial space occupant density air conditioning load calculation primary return air system
  • 相关文献

参考文献6

二级参考文献10

  • 1赵桂荣 马葆华.对本溪站前地下商场空调设计有关问题的探讨[A]..见:中国土木工程学会防护工程学会人防工程与地下空间委员会论文集[C].,1995..
  • 2陈自强 赖元雄.南方大厦洞天商场通风空调技术总结[J].人防工程,1986,(1).
  • 3中国建筑科学研究院 中国建筑业协会建筑节能专业委员会.GB 50189-2005 公共建筑节能设计标准[S].北京:中国建筑工业出版社,2005..
  • 4中国建筑科学研究院.GB/T 14294-93 组合式空调机组[S].北京:中国建筑工业出版社,1996
  • 5Kirkpatrick A T,Elleson J S.低温送风空调系统设计指南[M].汪训昌,译.北京:中国建筑工业出版社,1999
  • 6中华人民共和国建设部.GB 50155-92 采暖通风与空气调节术语标准[S].北京:中国计划出版社,1992
  • 7ASHRAE.ASHRAE handbook fundamentals[S].ASHRAE Inc,2004
  • 8李春安.某地下工程空调节能分析[J].暖通空调,1999,29(2):72-73. 被引量:3
  • 9闫斌,郭春信,程宝义,缪小平.舒适性空调室内设计参数的优化[J].暖通空调,1999,29(1):44-45. 被引量:46
  • 10杨盛旭,李刻铭,郭春信,朱志平.地下商场空调设计问题探讨[J].暖通空调,2004,34(2):44-47. 被引量:6

共引文献27