摘要
阐述金属氧化物避雷器的结构特点和工作原理,以500 kV东莞站#3主变变高C相避雷器和500 kV鹅博甲线线路A相避雷器两起避雷器故障为例,分析这种避雷器缺陷产生的原因,提出预防和及早期发现避雷器缺陷的应对措施。
The structural particulars and working principle of zinc-oxide arrestor is formulated. With the defects found in the 500 kV E-BO circuit I phase A arrestor and that of Transformer #3 HV-side arrestor in 500 kV Dongguan substation as examples, the reason that caused these defects is analyzed. Counter-measure for detecting and preventing these defects in advance is put forward.
出处
《广东输电与变电技术》
2011年第1期47-49,共3页
Guangdong Power Transmission Technology
关键词
500kV
避雷器
缺陷
红外测温
500 kV Arrestor Defects Infrared temperature measurement