地区小电源在110kV主网终端站并网对保护及自动装置的影响

Influence on Protection Configuration when Small Power Supply System Connected into 110 kV Terminal Substation
下载PDF
导出
摘要 地方小电源的接入,将系统由单端辐射型网络变成双端或多端有源系统,并网点的继电保护及自动装置的动作均受到影响。文中根据本地电网的实际运行需求和相关规程,通过对可能出现的系统故障进行分析,探讨了小电源并网对相关保护设备及自动装置的动作行为影响,针对性地提出了二次设备的配置方案,阐述了设备定值的有序配合。实践表明,整改后的方案提高了系统供电的可靠性,确保电网及小电源系统的安全稳定运行,为更多分布式电源的接入创造条件。 With small power supply system connected, the distribution system has developed from the traditional sim- ple single-source radial-network to a complicated multi-source network. The connected way to the earth of the termi- nal transformer, relay protection and automation device are affected. Based on the relevant procedures and the analy- sis of possible system failure,this paper disscused how the synchronized small power source affected the relevant pro- tection and automation device, and proposed a reasonable allocation plans for secondary equipment. Practice has proved that the plan will ensure the safety and stability of power system as well as small power supply system.
出处 《华北电力技术》 CAS 2011年第1期20-22,29,共4页 North China Electric Power
关键词 小电源 并网 解列 保护 自动装置 small power supply system integration into the power networks stepout relay protection automation device