应用流体网络分析法,对现行高层建筑防火规范第8章第8.3.2条表8.3.2-2中的风量控制数据进行了校验性计算,揭示了分别加压送风的流动特性。计算结果表明,向防烟楼梯间加压是徒劳的,因为加压送风会直接从防烟楼梯间的疏散外门流失。
By an air flow network analysis,calculates and verifies the data of air flow control in the table 8.3.2-2 of the item 8.3.2 of the chapter 8 in the present fire protection code of tall buildings.Reveals the flow characteristics of separate pressurization air supply.Calculating results show that it is useless to pressure to smoke prevention staircase,since pressurization supply air goes directly from evacuation exterior door.
出处
《暖通空调》
北大核心
2011年第1期64-70,共7页
Heating Ventilating & Air Conditioning
关键词
分别加压
疏散外门
节点平衡
闭合点
流量校正
separate pressurization
evacuation exterior door
node balance
closing difference
flow emendation