摘要
华电国际邹县发电厂WDPF-Ⅱ型分散控制系统自投产以来,手操站多次由自动(AUTO)方式切至就地(LOCAL)方式。通过分析,判断该异常现象是由于WDPF系统供电电源——不间断电源的输出频率突变引起的。希望能为同类型分散控制系统的故障分析提供借鉴。
Since the WDPF-II distributed control system of Huadian International Zouxian Power Plant had been put into operation,the MA station was switched over from AUTO mode into LOCAL mode many times.It was decided by analysis that the abnormal occurrence is caused due to that the output frequency of the UPS,which supplies power for the WDPF system,was varied rapidly.It is desired that the result can be used as reference for fault analysis of similar DCS system.
出处
《华电技术》
CAS
2011年第1期40-43,79,共4页
HUADIAN TECHNOLOGY
关键词
WDPF系统
手操站
不间断电源
频率
WDPF system
manual operation station(MA station)
uninterruptible power supply(UPS)
frequency