期刊文献+

基于向量比较原理的唯一稳态消谐法及在消除中性点接地电力系统铁磁谐振中的应用

Unique Steady-state Elimination Method Based on Vector Comparison Method and Its Application to Ferroresonance Elimination in Neutral Grounding System
下载PDF
导出
摘要 唯一稳态消谐法是近年出现的消除非线性系统谐振新的分析方法。该方法的基本思想是如果非线性系统存在一个非谐振的正常解,并且该系统具有唯一的稳态,则此时对应的条件就是系统不发生谐振的条件。将这一方法应用在消除中性点接地电力系统的铁磁谐振的分析中,以向量比较原理为工具,得到了相应的消谐条件。其结果表明,消除谐振的条件可以用一个常数矩阵的Hurwitz条件来决定,并用数值模拟进行验证,表明结果正确,同时也说明唯一稳态消谐法的有效性。 Unique steady-state elimination method is a new method for eliminating resonance in nonlinear system presented recently.Its basic idea is that if there is a normal(non-resonance) solution for the system,and the steady state of the system is unique,then the corresponding conditions are the conditions for eliminating resonance.This new method is applied to analyze the elimination of ferroresonance in neutral grounding system.Based on vector comparison method,the conditions for eliminating this ferroresonance are obtained,which can be determined by the Hurwitz conditions of some constant matrixes.The conclusions are proved correct by numerical simulation,and it shows the effectiveness of unique steady-state elimination method.
出处 《四川电力技术》 2011年第1期5-7,20,共4页 Sichuan Electric Power Technology
基金 国家自然科学基金资助项目(50477050)
关键词 电力系统 铁磁谐振 中性点接地系统 非线性系统 唯一稳态消谐法 power system ferroresonance neutral grounding system nonlinear system unique steady-state elimination method
  • 相关文献

参考文献8

二级参考文献24

  • 1常卫中,刘玄毅.直接接地系统铁磁谐振过电压计算分析[J].东北电力学院学报,1996,16(1):27-32. 被引量:7
  • 2Mork B A, Stuehm D L. Application of nonlinear dynamics and chaos to ferroresonance in distribution system. IEEE Trans. on Power Delivery, 1994, 9(2):1009- 1017
  • 3Tong Y K. DGC experience on ferroresonance in power transformers and voltage transformers on HV transmission systems, 1997 IEE Colloquium, 1997, 4/1-4/3
  • 4Vilcheck W S, Haddad M V. Voltage transformer ferroresonance in cogeneration substation. Proc. 1992 Pulp and Paper Industry Technical Conf: 148- 158
  • 5R Hoerauf, N Nichols.Avoiding potential transformer ferroresonant problems in industrial power systems.Proc. Industrial and Commercial Power Systems Technical Conf. USA, 1989:611-618
  • 6Ahdrei R G, Halley B R. Voltage transformer ferroresonance from an energy transfer standpoint. IEEE Trans on Power Delivery, 1989, 4(3): 1773-1778
  • 7Zahawi B A T AI, Emin Z, Tong Y K. Chaos in ferroresonant wound voltage transformer effect of core losses and universal circuit behaviour. IEE Proc Sci. Meas. Technol, 1998, 145(1): 39-43
  • 8Zahawi Z Emin B A T AI, Auckland D W, Tong Y K.Ferroresonance in electromagnetic voltage transformers:A study based on nonlinear dynamics. IEE Proc Gener.Transm. Distrib., 1997, 144(4): 383-387
  • 9Marti J R, Soudack A C. Ferroresonance in power systems: Fundamental solutions. IEE Proc-C, 1991,138(4): 321-329
  • 10Walling R A, Hartana R K. Reckard R M, et al.Performance of metal-oxide arresters exposed to ferroresonance in padmount transformers. IEEE Trans.on Power Delivery, 1994, 9(2): 788-795