双分裂导线在500kV重冰区线路中的应用 被引量:4

Application of Double-bundle Conductors in 500kV Transmission Lines in Heavy Icing Area
原文传递
导出
摘要 为了在广东电网500kV坪石—曲江送电线路的30mm及50mm重冰区选择满足技术要求且经济合理的导线截面和分裂型式,从输送容量、电磁环境、机械特性及工程投资等方面系统地介绍了该线路的导线选型论证。计算结果表明,采用双分裂大截面导线,电磁环境干扰值能满足规程要求;机械性能上,双分裂导线方案明显优于四分裂导线方案,并且能显著节省投资。因此,推荐该线路30mm及以上重冰区线段采用双分裂大截面导线。 The cross-section and bundle type of conductors are systematically demonstrated for the 500 kV Pingshi to Qujiang transmission line in 30 mm and 50 mm heavy icing area in terms of transmission capacity,electromagnetic environment,mechanical characteristics and project investment.The results show that the double-bundle conductors with large cross-section can satisfy the code requirement in interruption value of electromagnetic environment and is obviously superior to the four-bundle conductors in mechanical characteristics and can save investment significantly.The double-bundle conductors with large cross-section are therefore recommended for the power line in 30 mm and above heave icing areas.
出处 《电力建设》 2011年第1期49-53,共5页 Electric Power Construction
关键词 重冰区线路 导线选型 电磁环境 双分裂导线 四分裂导线 技术经济比较 transmission lines in heavy icing area conductor selection electromagnetic environment double-bundle conductor four-bundle conductor technical and economic comparison
  • 相关文献

参考文献8

  • 1广东省电力设计研究院.广东电网冰灾事故分析与建议研究报告[R].广州:广东省电力设计研究院,2008.
  • 2廖毅,潘春平,周冰.广东电网冰灾事故分析与应对措施[J].广东输电与变电技术,2008(5):1-9. 被引量:5
  • 3广东省电力设计研究院.500kV坪石B电厂三期至500kV曲江站线路工程提高抗冰能力方案初步设计说明书(S5071C-A0103-01)[R].广州:广东省电力设计研究院,2008.
  • 4潘春平.广东电网在建和新建工程提高抗冰能力的设计[J].广东输电与变电技术,2008(5):12-15. 被引量:1
  • 5DL/T5092-1999,110kV-500kV架空送电线路设计技术规程[S].1999.
  • 6Q/CSG11502-2008110kV-500kV架空输电线路设计技术规定(暂行)[S].
  • 7Q/CSG11503-2008,中重冰区架空输电线路设计技术规定(暂行)[S].
  • 8中国电力工程顾问集团公司,西南电力设计院.重覆冰架空输电线路设计技术规程(送审稿)及条文说明和编制说明[M].北京:中国电力工程顾问集团公司,2008.

共引文献14

同被引文献45

引证文献4

二级引证文献10

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部