摘要 为评估特快速暂态过电压(very fast transient overvoltage,VFTO)特性及其对主要电气设备的危害,结合我国西北电网中某750kV气体绝缘金属封闭开关设备(gas-insulated metal-enclosed switchgear,GIS)变电站,进行了大量的仿真计算,初步掌握了GIS内、外部主要部位VFTO的分布情况,并得出该变电站最大VFTO幅值在相关设备耐受能力范围内的结论。在此计算基础上进行了现场实测,准确掌握了750kV GIS变电站VFTO实际幅值、波形及频率等重要特性参数。现场实测结果对于750kV GIS中隔离开关的倒闸操作具有实际指导意义,同时也为1000kV交流特高压GIS设备中VFTO的实测及倒闸操作积累了经验和数据。 In order to evaluate the characteristics of very fast transient overvoltage(VFTO)and its harm to the main electrical equipment,a large number of simulating calculations have been carried out based on a 750 kV gas-insulated metal-enclosed switchwear(GIS) substation in Northwest Power Grid of China and the distribution of VFTO on main parts inside and outside of the GIS are determined.It is concluded that the maximum VFTO amplitude is within the withstanding capability of the relevant equipment of this substation.Based on in-situ measurement,the important characteristic parameters,such as the amplitude,waveform and frequency of VFTO of the 750 kV GIS substation are obtained.The in-situ measurements have instructive significance for the switching operation of disconnector of 750 kV GIS and will provide valuable experience and data for VFTO measurement and switching operation of 1 000 kV GIS.
作者 卢鹏
出处 《电力建设》 2011年第1期86-90,共5页 Electric Power Construction
关键词 750kV GIS 变电站 快速暂态过电压(VFTO) 过电压 隔离开关 750 kV gas-insulated metal-enclosed switchgear(GIS) substation very fast transient overvoltage(VFTO) overvoltage disconnector
  • 相关文献

参考文献5

二级参考文献32

  • 1王赞基.大型变压器线圈暂态分析的一个模型[J].清华大学学报(自然科学版),1993,33(1):25-32. 被引量:4
  • 2王赞基.变压器线圈中特快速暂态仿真的建模[J].中国电机工程学报,1996,16(5):299-305. 被引量:65
  • 3Nojima K, Ogawa S. Measurement of surge current and voltage waveforms using optical-transmission techniques[J]. IEE Proceedings, 1987, 134 (6):415-422.
  • 4Fujita S, Hosokawa N, Shibuya Y. Experimental investigation of high frequency voltage oscillations in transformer winding[J]. IEEE Trans on Power Delivery, 1998, 13(4):1 201-1 207.
  • 5Kumar V, Thomas M J, Naidu M S. VFTO computation in a 420 kV GIS[A]. Conference Record of International Symposium on High Voltage Engineering,London, 1999.
  • 6Popov M, van der Sluis L, Paap G C, et al. Computation of very fast transient overvoltages in transformer windings[J]. IEEE Trans on Power Delivery, 2003, 18(4):1 268-1 274.
  • 7Gharehpetian G B, Mohseni H, Moller K. Hybrid modeling of inhomogeneous transformer windings for very fast transient overvoltage studies[J]. IEEE Trans on Power Delivery, 1998, 13(1):157-163.
  • 8Working Group 33/13-09. Very fast transient phenomena associated with gas insulated substation[C]. CIGRE Report 33-13. Paris, 1988.
  • 9V Vinod Kumar. VFTO computation in a 420 kV GIS[C]. IEE Conference Publication 1 467. Eleventh ISH. London, UK,1999: 1319-1322.
  • 10J Grandl. Studies of very fast transients (VFT) in a 765 kV substation[C]. CIGRE Report 33-12. Paris, 1988.